Posi-Bbpr (Gps) Models - Burkert 3004 Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour 3004:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
POSI-BBPR (GPS) : description
The GPS version includes BBPR and positioning
Battery position backup:
This system insure a return to predefined position in case of power failure. The predefined position can be set close (default) or
open.
Positioning:
0-10 V: In case of outside event, absence of control signal (accidental wires cut for example) but in the presence of power, the actua-
tor will travel to defined position (open or closed valve). As standard our actuators will close themselves with absence of control
signal but there are other possibilities on request.
4-20 mA: In case of outside event, absence of setpoint signal (accidental wires cut for example) but in presence of power, the actua-
tor will stay in its position
The factory default configuration is "normally closed"
Actuator voltage
Battery voltage
Battery capacity
Charging current
Maximum battery charge duration
Rep
Terminals Description
B1
« Close » button
B2
« Mem» button
B3
« Open » button
C1
A,C
Motor connector
C2
67,68
Failure feedback relay
C3
65,66
Charging status feedback relay
F (+)
C4
F (-)
Battery connector
T (+)
17 (-)
C5
power supply connector
18 (+)
15(-)
Positioning setpoint signal con-
C6
16(+)
nector (0-10 V or 4-20 mA)
13A(+)
Positioning feedback signal con-
C7
13B(+)
nector.
14(-)
13A=0-10 V et 13B=4-20 mA
C8
A,0,B
RS485 connector
J1
CV1
Bluetooth
LED
Description
MANU manual / Bluetooth
HORO Weekly scheduler functioning mode
APPR
Learning mode selected
POSI
Positioning mode
3004 • Rev. 2109/06 • 00806090
function.
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
20 V to 30 V AC 50/60 Hz and 20 V to 48 V DC
24 V DC
Charging status feedback relay (65/66)
600 mAh
Failure feedback relay (67/68)
180 mA
Temperature
3,5 h
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 07 ATEX 6078X / LCIE 22.0001X
Ambient temperature: -10 °C to +40 °C
®
activation jumper
®
functioning mode
C6
C7
Error detected:
 Timestamp memory empty/scheduler selected
 Clock failure
ERROR
 Excessive temperature
 Excessive torque
Power supply:
 Slow blinking (1 s) : charged battery
ACT
 Rapid blinking (0.5 s) : battery charging
APPR1
Open position stored (confirmation)
APPR2
Closed position stored (confirmation)
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C à +40 °C
J1
C5
C4
C8
C3
C2
C1
LED
B1
B2
B3
51