Air Flow Direction - Daikin BRC1E71 Manuel D'installation

Télécommande
Masquer les pouces Voir aussi pour BRC1E71:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7-4
Press On/Off button within 10 seconds,
and the test operation starts.
Monitor the operation of the indoor unit
for a minimum of 10 minutes. During
test operation, the indoor unit will
continue to cool regardless of the
temperature setpoint and room
temperature.
Note) In the case of above-men-
tioned procedures
7-4
in reverse order, test
operation can start as well.
7-5
Press Menu/OK button in the basic
screen. Main menu is displayed.
7-6
In the case of a model having air fl ow
direction function, select

Air Flow Direction

and check that air fl ow direction is
actuated according to the setting.
For operation of air fl ow direction
setting, see the operation manual.
7-7
After the operation of air fl ow direction
is confi rmed, press Menu/OK button.
Basic screen returns.
7-8
Press and hold Cancel button for
4 seconds or longer in the basic
screen.
Service settings menu is displayed.
7-9
Select
Test Operation
settings menu, and press Menu/OK
button. Basic screen returns and
normal operation is conducted.
Note) The test operation will automat-
ically fi nish in 30 minuites.
7-10
Check the functions according to the
operation manual.
7-11
When the decorative panel is not
installed, shut off the power supply
after the test operation fi nishes.
If construction activities are planned within
the space following the test operation
procedure, recommend to the customer
that the air conditioner is not operated to
prevent contamination from paints, drywall
dust and other air borne materials.
16
7-
7-
7-3
and
7-
7-
in the main menu
7-
in the service
7-
4
5
Cool
Set temperature
28
°C
Test Operation
<Main Menu screen>
6
MainMenu
1/2
Air Flow Direction
Ventilation
Schedule
Off Timer
Celsius / Fahrenheit
Maintenance Information
Setting
7
Air Flow Direction
Swing
Setting
8
Cool
Set temperature
28
°C
Test Operation
9
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Setting
<Basic screen>
Press On/Off button
(within 10 seconds).
Press Menu/OK button.
Press Menu/OK button.
Change the air fl ow
direction by using
(Up/Down)button.
Press Menu/OK button.
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
English