Initialization
4.1

Initialization of rotary actuators

Set the 1st parameter ("YFCT") in rotary actuators at normal direction of
action of the drive to "ncSt" or at inverse direction of action to "-ncSt".
Start initialization as usual by "INITA".
4.2

Initialization of linear actuators

Set the 1st parameter ("YFCT") of the positioner to "ncSLL".
Start initialization as usual by "INITA".
NOTE
The "ncSLL" parameter value only exists with devices in the 6DR5xxx
series and only with firmware versions > C4. For devices of series
6DR5xxx and firmware versions < C5 (YAGL) set it to 90°. This is also
required for devices of the 6DR4xxx series. The resulting non-linearities
can be corrected with the programmable curve by setting the parameter
value "SFCT" to "FrEE" and the individual coordinate points respectively.