Technical specifications |
Type
Output
step
[kW]
SFS23E08
2,7/5,4/8,1
SFS30E12
3,9/7,8/11,7
SFS38E16
5,4/10,8/16,2
SFS56E23
7,8/15,6/23,4
Technical specifications |
Typ
Output*
[kW]
SFS23WL
13,3
SFS30WL
19,9
23,1
SFS38WL
SFS56WL
29,4
*
1
) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m².
) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
2
*
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
3
*
4
) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
*
) Extension possible up to 3000 mm (extension without fans).
5
Protection class: IP20.
CE compliant.
12
Electrical heat - SFS E
∆t
Airflow
*2
[m
/h]
[°C]
3
1050/2300
23/11
1400/3000
25/12
1800/3800
27/13
2700/5600
26/12
Water heat - SFS WL, Coil for low water temperature <80 °C
∆t
Output*
Airflow
3
4
[kW]
[m
/h]
3
[°C]
22,3
1050/2300 22/17
33
1400/3000 25/20
39,1
1800/3800 23/18
49,7
2700/5600 20/20
SFS
3
Sound
Voltage [V]
level*
Amperage [A]
1
[dB(A)]
(control)
230V~/2,3
60
61
230V~/3,1
230V~/4,8
62
230V~/7,0
63
∆t
Water
*2,3
*2,4
volume
[l]
[°C]
37/29
3,0
41/33
4,4
38/31
4,4
34/26
4,4
Voltage [V]
Length
*5
Weight
Amperage [A]
(heat)
[mm]
[kg]
400V3~/11,7
2200
75
400V3~/16,9
2200
80
400V3~/23,4
2200
80
400V3~/33,8
2200
90
2
Sound
Voltage
Amperage
level*
1
[dB(A)]
[V]
[A]
60
230V~
2,3
61
230V~
3,1
62
230V~
4,8
63
230V~
7,0
Length
Weight
*5
[mm]
[kg]
2200
75
2200
80
2200
80
2200
90