Section Ii: Installation And Maintenance; Description Of The Unit; Structural Features; Available Installations - Hitecsa EWMIM 117 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

II
SECTION II: INSTALLATION AND
MAINTENANCE
According to Regulation (UE) N. 517/2014 issued on 16 april 2014
Operators of equipment which is required to be checked for leaks
pursuant to Article 4(1), shall establish and maintain records for each
piece of such equipment specifying the information provided for Art.
6(1).
The operator is the owner of the equipment or system. The operator
can formally delegate a person or external company (by way of written
contract) to control the equipment or system.
II.1

DESCRIPTION OF THE UNIT

II.1.1

STRUCTURAL FEATURES

o Load-bearing structure and panels in galvanised and RAL 9018
painted sheet metal; galvanised steel sheet metal base.
o -Hermetic scroll type rotary compressors with inverter activation to
control variable capacity from 30% to 120% of the nominal capacity with
peak current reduction during the start-up phase and power factor
correction of the automatic user to the network. They are complete with
external thermal protection and crankcase heater activated
automatically when the unit stops (as long as the electrical supply to the
unit is preserved).
o -Adequately insulated, braze-welded plate water side heat exchange
in stainless steel complete with anti-freeze heater.
o -Air side heat exchanger featuring finned coil with copper pipes and
aluminium fins, with hydrophilic surface treatment.
o -Electric axial fans with external rotor, supplied with internal thermal
protection and complete with protection mesh. Proportional electronic
device for pressure regulation and continuous regulation of the rotation
speed of the fans.
o -Male threaded hydraulic connections.
o -Differential pressure switch that protect the unit from any water flow
interruptions.
o -Outdoor air temperature probe
o -Cooling circuit made with an annealed copper pipe (EN 12735-1-2)
complete with: dryer filter, load connections, high pressure side
pressure switch, pressure transducer on both the high and low pressure
sides, electronic thermostatic expansion valve , cycle inversion valve,
liquid receiver, gas separator and check valve.
o Unit with IP24 protection rating.
o Control with AdaptiveFunction Plus operation.
o The unit is complete with a charge of R410A refrigerant.
II.1.2

AVAILABLE INSTALLATIONS

Pump P0 – Set up with a 3-speed electronic circulator.
Pump PI0 – Set up with an electronic circulator with continuous
adjustment (variable capacity of the system).
Pump P1 – Set-up with a single pump standard head.
Tank&Pump ASP0 – Set up with inertial buffer tank and 3-speed
electronic circulator.
Tank&Pump ASPI0 – Set up with inertial buffer tank, electronic
circulator and continuous speed regulation (variable flow rate on the
system).
Tank&Pump ASP1 – Set up with inertial buffer tank and single basic
head pressure pump.
II.2

ELECTRICAL CONTROL BOARD

o Electrical panel can be accessed by opening the front panel, in
compliance with IEC Standards in force, fitted with opening and closing
via specific tool.
o Complete with:
electrical wiring arranged for power supply 400-3ph+N-50Hz;
auxiliary circuit power supply 230V-1ph+N-50Hz derived from main
power supply;
main power supply switch with interlocking safety door isolator;
automatic compressor protection switch;
auxiliary circuit protection fuse;
compressor power contactor;
remote machine commands and controls.
o Programmable microprocessor electronic board handled by the
keyboard inserted in the machine.
o This electronic board performs the following functions:
Adjustment and control of the machine water output temperature
set-points; of the cycle inversion; of the safety timings; of the circulation
pump; of the system pump and compressor hour-run meter; of the
electronic anti-freeze protection with automatic activation if the machine
is off; of the functions that regulate the intervention method of the
individual parts forming the machine;

SECTION II: INSTALLATION AND MAINTENANCE

complete protection of the unit, possible shutdown and display of all
the triggered alarms;
total compressor and inverter protection by means of continuously
monitoring the current absorbed by the compressor and operating
pressures. The compressor can modulate automatically, regardless of
the request if it goes out of its proper field of operation.
RFI filter for conducted electromagnetic interference.
compressor protection phase sequence monitor;
unit protection against low or high phase power supply voltage;
display the programmed set-points via the display; the in/out water
temperature via the display; the alarms via the display; the chiller or
heat pump operation via Led;
self-diagnosis with continuous monitoring of the unit functioning
status.
user interface menu;
alarm code and description;
alarm history management (menu protected by factory password).
o In particular, for every alarm, the following are memorised:
date and time of intervention;
 alarm code and description;
in/out water temperature values as soon as the alarm was
triggered;
alarm delay time from the switch-on of the connected device;
compressor status at the time of the alarm;
o Advanced functions:
 set-up for serial connection (KRS485, KFTT10, KBE, KBM, KUSB
accessory);
 possibility of having a digital input for remote management of the
double set-point;
 possibility to have an analogue input for the shifting Set-point via a 4-
20mA remote signal;
 configured to manage time slots and work parameters with the
possibility of daily/weekly operation planning;
 check-up and monitoring of scheduled maintenance status;
 computer-assisted unit testing;
 self-diagnosis with continuous monitoring of the unit functioning
status.
○ Compressor drive control serial connection to the programmable
electronic board.
o Set-point regulation via the AdaptiveFunction Plus with two
options:
 fixed set-point (Precision option);
 set-point sliding (Economy option).
II.3

SPARE PARTS AND ACCESSORIES

IMPORTANT!
Only Use original spare parts and accessories.
HITECSA shall not be held liable for damage
caused by tampering with or work carried out by
unauthorised personnel or malfunctions caused by
the use of non-original spare parts or accessories.
II.3.1

FACTORY FITTED ACCESSORIES

FDL - Forced Download Compressors function. Compressor modulation
to limit the absorbed current and power (digital input). Also used as a
"night mode" function to limit noise during night-time operation.
SIL
Soundproof technical compartment and compressor hood.
FI15 – Condensate control with low consumption EC electronic fans.
RAE – Circulator or pump antifreeze(P0/PI0) resistance (P1).
RAS – Storage anti-freeze resistance.
RAP - Unit with copper/pre-painted aluminium condensation coils.
BRR - Unit with copper/copper condensation coils.
DSP – Double set-point via digital input (incompatible with the CS
accessory) only with Precision setting.
CS – Shifting set-point via 4-20 mA analogue signal (incompatible with
the DSP accessory and with the compensation function with outdoor
air). Only with Precision setting.
26

Publicité

Table des Matières
loading

Table des Matières