I.2.1 Machine Identification; I.3 Declared Conditions Of Use; I.3.1 Functioning Limits - Hitecsa EWMIM 117 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

I.2.1
MACHINE IDENTIFICATION
The units feature a serial number plate located on the side which
includes machine identification data.
I.3
DECLARED CONDITIONS OF USE
EWMIM units are packaged cooling cycle reversible heat pumps with air
evaporation/condensation and axial fans complete with a hydraulic
pump.
The units are air cooled packaged water chillers and helical fans
with axial fans.
They are suitable in air conditioning installations and industrial
processes where chilled and hot water is required, not for human
consumption.
The units are designed for outdoor installation.
DANGER!
The machine has been designed and manufactured
solely and exclusively to function as an air
evaporation heat pump; any other use is strictly
PROHIBITED. Installing the machine in an explosive
environment is prohibited.
DANGER!
The machine is designed for outdoor installation.
Segregate the unit if installed in areas accessible to
persons under 14 years of age.
IMPORTANT!
The unit will function correctly only if the
instructions for use are scrupulously followed, if
the specified clearances are complied with during
installation, as well as the use restrictions indicated
in this manual.

I.3.1 FUNCTIONING LIMITS

Summer mode EWMIM 117÷128
Winter mode EWMIM 117÷128
T (°C) = Air temperature (B.S.).
t (°C) = Temperature of the water produced.
Standard functioning
Operation FI15
In summer mode:
Maximum water inlet temperature 25°C.
In winter mode:
Maximum water inlet temperature 55°C
Permitted temperature differentials through the heat exchangers
○ Temperature differential ∆T = 4 ÷ 8°C.
○ Minimun water pressure 0,5 Barg.
○ Maximum water pressure 6 Barg.
N.B.:
For evaporator outlet water at a temperature below 5°C, please contact
the HITECSA pre-sales service before ordering.
In the permitted field of operation, the compressor and inverter are
protected by a controller by means of continuous monitoring of the
current absorbed by the compressor, operating pressure and output
temperature. The compressor can modulate the rotation speed
automatically, regardless of the set-point request if it goes out of its
proper field of operation.
23
SECTION I: USER

Publicité

Table des Matières
loading

Table des Matières