6.3
GENERAL PLENUM AND DUCTING - MINIMUM CLEARANCE TO
COMBUSTIBLES
EN
All plenum and ducting clearances must satisfy specifi cation set forth in CAN/CSA-B365-10 and NFPA211.
CLEARANCE
TO
COMBUSTIBLES
TOP
BOTTOM/
SIDES
* FOR CHMF150 ONLY. Clearance can be reduced from 6" (152mm) to a minimum of 3" (76mm), providing that shielding with the fol-
lowing specifi cations is employed. Ceiling height can be reduced to 6ft. (1.8m) when shielding specifi cations are met.
* FOR CHMF200 ONLY. Minimum ceiling height for installation can be reduced to 6' 9" (2.06m) provided shielding specifi cations in
Section 6.3.2 are employed and a clearance of 6" (152mm) is maintained between the top surface of the plenum and initial 6ft. (1.8m)
of duct run.

6.3.1 CHMF150 SHIELDING SPECIFICATIONS

Shield must be constructed of sheet metal with a minimum thickness of 26 gauge.
Shield to be spaced out from combustible surface between 7/8" (22mm) and 1" (25mm), using non-combus-
tible spacers (air gap between combustible surface and shield must be maintained).
Shield dimensions and locations must protect the area illustrated in the diagram below.
1" MIN
(25mm)
4" MIN
(102mm)
W415-1506 / C / 02.15.18
SECTION
A
B
C
6" (152mm) *
6" (152mm)
1" (25mm)
18" (457mm)
6" (152mm)
1" (25mm)
NOTE:
The clearance of
return air ducts,
including main
ducts and
branch ducts,
from combus-
tible materials
within 6 ft.
(1.8m) of the
plenum shall
be not less
than 3" (75mm)
COMBUSTIBLE SURFACE
SHIELD
PLENUM
IMPORTANT:
Minimum ceiling heights required: • CHMF150 6ft 3in (1.9m)
CLEARANCE TO COMBUSTIBLES
1
6" (152mm)
A
2
40"
(1016mm)
72"
(1829mm)
1 See shielding specifica-
tions below for reduced
clearances and/or ceiling
height.
2 See plenum diagram
below for minimum dimen-
sions.
3" MIN
(76mm)
PLENUM
4" MIN
(102mm)
• CHMF200 7ft (2.13m)
1"
(25mm)
B
C
>72"
(1829mm)
*Drawing not to scale.
COMBUSTIBLE SURFACE
SHIELD
72" MIN
(1829mm)
*Drawing not to scale.
1" MIN
(25mm)