4. Mounting suggestion
5. Connection
Cable connection in the actuator cavity.
Permitted voltage drop in the actuator cable is
max. 2V.
When MotorLink™ max. 50m cable.
Europe
For connection use WindowMaster standard
WLL extention cable (to be ordered
seperately).
If the chain actuator is used in connection with
smoke ventilation, the plugs mounted are to
be cut off, and replaced by plugs/connectors
approved for smoke ventilation.
Other countries
For connection use cables and plugs
according to Nationall Regulations.
Important! According to national regulation,
EN 60204-1 and the directive of machinery,
the yellow-green cable must not be used for
anything else that earth (PE).
Connection of actuators
For connetion to control unit
see the Control Unit instruction
±24VDC WMB 811-1
Single
±24V DC WMB 811-2/812-2
Synchro
MotorLink™
WMB 811-n/812-n
4. Montagevorschlag
Kabelanschluss im Hohlraum des Antriebes.
Der zulässige max. Spannungsabfall auf der
Motorleitung beträgt 2V.
Bei MotorLink™max. 50m Leitung.
Europa
Als eine weiterführende Leitung/Verlängerung ist
eine WLL Standardleitung lieferbar und
gesondert bestellt werden.
Wenn der Ketten-antrieb im Zusammen-hang mit
RWA verwendet werden soll, sind die montierten
Stecker abschneiden, und stattdessen sollen
RWA genehmigte Stecker/Muffen verwendet
werden.
Anderen Ländern
Für den Anschluss müssen Kabel und Stecker
nach die Nationale Richtlinien eingehalten
werden.
Wichtig! Nach den nationalen Vorschriften, EN
60204-1 und der Maschinendirektive, darf die
grün-gelbe Ader zu keinem anderen Zweck als
Erde (PE) verwendet werden.
Verbindung von Antrieben
Für den Anschluss an die Steuereinheit
siehe Steuereinheitanleitung
Cable colour
Kabelfarbe
Kabelfarve
WH
WS
GR
BR
HV
Maintenance
Open
cable
Auf
Åbn
+
Sync
-
ML-
*
comm
WEC / WBC / WCC
WLC / WLS / WBS
WSC / xxM
5. Anschluss
Single WMB
+/-
+/-
WCC xxx
WUC xxx
-/+
WSC xxx
MotorLink™
Single WMB
+ +
WEC / WBC / WCC
ML-comm
WLC / WLS / WBS
-
WSC / xxM
±24V DC
Synchro WMB
+/-
+/-
WCC xxx
Maintenance cable
WUC xxx
-/+
WSC xxx
MotorLink™
Synchro WMB
+ +
ML-comm
-
4. Monteringsforslag
5. Tilslutning
Kabeltilslutning i hulrum på motor.
Det tilladelige spændingstab på motorled-
ningen må max. være 2V.
Ved MotorLink™ max. 50m kabel.
Europa
Forlængerkabel WLL kan leveres som
standardvare og skal bestilles separat.
Såfremt kædemotor anvendes i forbindelse
med brandventilation, skal de fabriksmonterede
stik klippes af, og der skal i stedet anvendes
stik/muffer godkendt til brandventilation.
Andre lande
For tilslutning anvendes kabler og stik iht. de
gældende nationale regler.
Vigtigt! I henhold til stærkstrømsreglementet,
DS EN 60204-1 og maskindirektivet må den
gulgrønne beskyttelsesleder ikke anvendes til
andet end jord (PE).
Tilslutning af motorer
For tilslutning til styreenhed
se styreenhedsvejledningen
WMB 811-1
±24V DC
Maintenance cable
WMB 811-1
WMB 811-2
WMB 812-2
SYNC
WMB 811-2
WMB 812-2
M