BNI IOL-314-S52-P012 / BNI IOL-314-S52-P071
Network interface – Digital hub
Electrical connection (continued)
I/O-Port (X00...X07)
Port X07 can be configured as a standard I/O port
or as an extension port.
Socket
Pin
Standard
I/O-Port
(X00...X07)
1
+24 V, sensor
2
5
2
Digital input/
1
3
3
GND, sensor
4
supply, inputs,
Top view of M12
socket, A-coded
4
Digital input/
5
For the digital sensor inputs, see guideline via
inputs EN 61131-2, type 1 and type 3.
UL requirements
The power supply has to be an isolated type or SELV type.
Power Ratings
Power input, nominal
rated voltage 24 V DC
BNI IOL-...-P012
– 130 mA maximum
consumption
– 4 A including all output loads
BNI IOL-...-P071
– 130 mA maximum
consumption
– 16 A including all output loads
Power output, nominal
– max. 1,4
rated voltage 24 V DC
BNI IOL-...-P071
Digital output, nominal
– 2 A max/point (port)
rated voltage 24 V DC
– 4 A or less per unit
(BNI IOL-...-P012)
Digital output, nominal
– 4 A max/point (port)
rated voltage 24 V DC
– 16 A or less per unit
(BNI IOL-...-P071)
Cleaning
Clean the product only with dry cloth or cloth dampened
only with water!
www.balluff.com
Signal
Extension
port (X07)
+24 V, sensor/
supply
module supply
+24 V, actuator
output
supply
GND, sensor/
actuator supply
outputs
C/Q
output
communication
line
FE
UL requirements (continued)
Cord Sizes
Power In cord assembly:
Listed or R/C (CYJV2/8) cord assembly with threaded
female M12 L-coded connector rated 24 V minimum, 16 A
minimum for all models. Cord Listed S, SJ, SO, ST, SV, or
R/C (AVLV2) marked or specified in UL style page as
suitable for external interconnection rated 300 V minimum,
14 AWG minimum unless marked with maximum load
current and overcurrent protection for the cord in
accordance with table below.
Communication/Power In cord assembly:
Listed (CYJV/7) or R/C (CYJV2/8) cord assembly by Balluff
with threaded male A-coded M12 connector rated 24 V
minimum, 2 A minimum. R/C (AVLV2) marked or specified
in UL style page as suitable for external interconnection
28 AWG minimum, 300 V minimum cord. May be provided
separately as an accessory.
Communication cord assembly:
Listed (CYJV/7) or R/C (CYJV2/8) cord assembly by Balluff
with threaded female A-coded M12 connector rated 24 V
minimum, 2 A minimum. R/C (AVLV2) marked or specified
in UL style page as suitable for external interconnection
28 AWG minimum, 300 V minimum cord. May be provided
separately as an accessory.
In/Out cord assembly:
Listed (CYJV/7) or R/C (CYJV2/8) cord assembly by Balluff
with threaded male A-coded M12 connector rated 24 V
minimum, 2 A minimum. R/C (AVLV2) marked or specified
in UL style page as suitable for external interconnection
Cord rated 300 V minimum, 24 AWG minimum unless
marked with maximum load current and overcurrent
protection for the cord in accordance with the table in
markings:
Cord
14 14 16 18 20 22 24 26 28 30
conductor
size, AWG
Overcurrent
16 12 8 5.6 5
protection
maximum
ampere rating,
Amps
Maximum
16 9
8 5.6 4 2.4 1.6 0.8 0.6 0.4
load, Amps
May be provided separately as an accessory.
3
2
1 0.8 0.5
english
4