Balluff BNI IOL-314-S52-P012 Mode D'emploi page 8

Masquer les pouces Voir aussi pour BNI IOL-314-S52-P012:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

BNI IOL-314-S52-P012 / BNI IOL-314-S52-P071
Network interface – Digital hub
Electrical connection (continued)
Power supply
NOTICE
Unwanted voltage dips
Non-separated electric circuits of the power supplies for
sensor and actuator can lead to unwanted voltage dips
of the sensor supply when switching actuators.
► Fuse the power supplies for sensors and actuators
separately.
► Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
NOTICE
Overcurrent
Defective or missing fuses in the power supply for sensor
and actuator will damage them.
► Use a fuse or intelligent power supply (current
monitoring designed for max. 4 A for BNI IOL-...-
-P012 or 16 A for BNI IOL-...-P071).
► Connect the protective earth conductor to the FE
terminal.
► Connect the incoming IO-Link line to the sensor hub.
NOTICE
Loss of function and property damage
Improper installation, e.g. due to misconnection or
incorrect polarity of the connections, can result in a loss
of the function and property damage.
► Take measures to prevent misconnection or polarity
reversal.
► Prevent tampering at the connections.
► Never exceed the value of 36 V between any of the
pins.
If possible, supply power to the sensor/module
and actuator using an independent power source
to ensure independent operation in the event of a
power failure.
For UL: observe cable requirements and power
supply requirements (siehe section
UL requirements)!
3
english
The supply voltage for the module is provided via the
IO-Link interface from the higher-level IO-Link master.
There are three different supply voltages: U
U
:
A
U
supplies the module and also the connected
S1
sensors. (Variant ...P012).
U
supplies the module only (Variant ...P071).
S1
U
supplies the connected sensors. (Variant ...P071).
S2
U
is the supply for the digital outputs.
A
IO-Link interface (XF1/
)
Plug
Pin
...-P012
1
Supply voltage
1
for the module
and connected
BNIXXXX
2
4
sensors (U
2
Supply voltage
3
for actuators
Top view of M12
(U
)
A
plug, A-coded
3
00
01
4
C/Q, IO-Link data transmission
Auxiliary voltage connection (XD1)
The BNI IOL-314-S52-P071 variant has an L-coded M12
00
01
auxiliary voltage connection. This connection allows more
power to be supplied for the sensor and actuator systems.
Plug
Pin
Signal
00
01
1
Power supply U
2
GND, reference potential U
3
GND, reference potential U
00
4
01
Actuator supply U
5
Function ground
Top view of M12
plug, L-coded
Current limitation when using the extension port
Variant BNI IOL-314-S52-P012
Observe the current limitation: The output is split 1:1
between the first and second device.
Variant BNI IOL-314-S52-P071
There is no current limitation to consider because the
current for the second device is supplied independently
via the auxiliary voltage connection.
, U
and
S1
S2
Signal BNI IOL-...
...-P071
Supply voltage
for the module
(U
)
S1
)
S1
GND, reference potential
00
01
channel
00
01
00
01
S2
A
S2
00
0 1
A