- in environments with the presence of explosive gaseous substances;
- outdoors and therefore where there are atmospheric agents;
- near heat sources (direct sunlight,heating systems, incandescent lights, etc.)
- near air currents (near doors, windows, air-conditioning/heating systems, etc.) exceeding speeds of
0.2 m/sec.
- remove the wooden supports at the base (used for transport) and assemble the adjustable feet (Rif.
2), positioning them in such a way as to bring the unit to a horizontal position. Use a spirit level (Rif. 1)
to check this. If the unit is moved, repeat the spirit level check.
- before connecting the unit up to the electricity, ensure that the plate data corresponds to the
characteristics of the electrical system to which it is to be connected.
- for correct unit operation, the environmental relative humidity and temperature must be in line with the
parameters specified by standards EN ISO 23953 -1/2, namely Climatic Class 3 (+25°C; U.R. 60%).
- check that the ventilation apertures of the condenser unit are not blocked - version with built-in unit.
ATTENTION!: Multiplex up to 3 cabinets on the same electrical and refrigeration supply line (1
master + 2 slaves)
Note:All these operations should be performed by specialised technical personnel.

8. Multiplexing of cabinets (Fig. 11)

To multiplex two or more cabinets, act as follows:
- Remove the sides
- Position the cabinets side by side
- Remove the back panels to gain access to the rise holes
- Join the rises and brackets using the screws supplied
- Replace the back panels.
MULTIPLEX KIT
Ref.
Code
Q.ty
1
02940652
2
04711030
3
04711041
4
04230600
5
04711040
6
04480112
7
04711098
8
04230400
9
04480103
10
02940045
11
04715051
12
04231100

9. Electrical connection (Fig. 14 - Fig. 15 - Fig. 16)

- the electrical system must be earthed.
- First check that the voltage supply is as specified on the plate data (Fig. 2)
- The unit must be protected upstream by an automatic omnipolar thermomagnetic switch with
appropriate characteristics. This must also act as a general line disconnection switch.
- Instruct the operator as to the switch position in order that it can be reached quickly in an
EMERGENCY.
- To guarantee correct operation, the maximum voltage variation must be between +/- 6% of the
nominal value.
- Check that the power line has appropriate section cables, is protected against overcurrent and
dispersions towards earth, in compliance with current standards.
- The installer must supply the anchorage devices for all cables in and out of the unit.
- For power lines exceeding 4-5 metres in length, increase the cable section accordingly.
- In the event of an interruption to the electricity supply, check that all store electrical appliances can
reboot without causing the overload protections to intervene. If not, alter the system in order to
differentiate between the start-up of the various devices.
05060104 01 01/09/2015
Description
8
Handrail alignment plug D 4
2
Screws TCEI M8X80
1
Screws TCEI M8X50
7
Hexagonal nut M8
4
Screws TCEI M8X35
8
Washer D 8.5x24
4
Screws TCEI M8X25
2
Hexagonal nut M6
4
Washer D 6x12
2
Lamp alignment plug D 3
3
Screws TC M5X25
3
Hexagonal nut M5
Pelican
English
31