Health And Safety; How The Calorex 'Series 3 Variheat' System Works - Calorex VARIHEAT VH3 AA600 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Health and Safety

This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety.
Children should be supervised to ensure that they do not play with the appliance.

1.0 HOW THE CALOREX 'SERIES 3 VARIHEAT' SYSTEM WORKS.

The Calorex 'SERIES 3 VARIHEAT' range consists of 4 models: 600/900/1200/1500.
The model number increases in relation to the recirculated air flow from model 600 at 2000 m³/h to model
1500 at 4300 m³/h.
All models are fitted with either one or two "console fixing service panels" These allow for the console to be fixed to
the Variheat 3. These service panels can be fitted on any face of the machine.
When optional fresh air box is fitted, all models have the facility to exhaust a percentage of the recirculating
air and introduce a slightly lesser amount of fresh air (slight differential creates a negative pressure on
pool hall to localise pool environment and protect the building fabric).
An optional "negative pressure box" is also available. This exhausts a percentage of the circulationg air without
introducing fresh air to the pool hall.
All AW models are fitted with a fully controlled low pressure hot water air heating battery and a pool water heat
exchanger.
Provision is made for an external heat source to be initiated by the 'SERIES 3 VARIHEAT' controller.
All AW models have air and water heat exchangers recovering energy from the refrigerated dehumidification
process. These are also fully controlled with priority given to water.
Optional, factory fitted frost protection kits are available, these kit protect the LPHW from freezing by closing the
dampers to min when the ambient temperature is below 6ºC. The first kit controls the machine dampers. A second
kit controls the machine dampers and also a remote damper fitted by the customer in the installation ductwork.