3.2.3 POOL & AIR TEMPERATURE AND HUMIDITY CONTROLS
POOL WATER TEMPERATURE & HUMIDITY DIGITAL CONTROLLERS AND AIR DIGITAL
CONTROLLER ON AA MACHINE WITHOUT AIR HEATING
 
 
 
To Program the Set Point. Press down P, SP1 and Set Point value will be displayed alternately. 
Press the    or    key to change the value of SP1. Once the desired value is displayed press P to memorise 
the value. The display will revert to the present reading.   
NOTE: If anything else shows on the display leave alone for 1 minute until the display returns to normal. 
 
AIR TEMPERATURE DIGITAL CONTROLLER AW AND AA MACHINES WITH AIR HEATING
The digital controller for controlling air temperature can be changed as follows:-  
To program the set point, press P button once and release it. SP1 (set point) and set point value 
e.g. 28 will be displayed alternately. Press P again AL1 (-4.5) will show. This is the difference between 
the set point and AL1 plus a constant 0.5 e.g. 28 - 4.5 + 0.5 = 24ºC (unoccupied) SP1 and AL1 can be 
changed in the same way as described for humidity and air. 
NOTE: AL1 can only be set -1 to -10 below SP1 value. 
 
If the reading on the digital controller is not the same as the actual pool hall temperature, water 
temperature or relative humidity it may be necessary to program an offset into the digital controller. See 
technical manual. 
 
FRESH AIR BOX
AUTO
Opens dampers and switches on fan when demand for dehumidification (OUT 2) and/or high 
temperature OUT 3 (OUT 2 on AA version without time clock). Machine must be in occupied 
mode to close Relay 4 and to bring on fan and open damper motor. 
 
MAX
Opens dampers and brings on fresh air fan to provide full fresh air at all times, even in 
unoccupied mode.
 
MIN
Turns off fresh air fan and closes dampers to minimum position.
 
NOTE
On machines with LPHW, if the optional frost protection stat is fitted, the operation of the 
dampers will be inhibited when the ambient temperature is below 6ºC.
 
NEGATIVE PRESSURE BOX
AUTO
Opens dampers and switches on fan when demand for dehumidification (OUT 2) and/or high 
temperature OUT 3 (OUT 2 on AA version without time clock). Machine must be in occupied 
mode to close Relay 4 and to bring on fan and open damper motor. 
 
MAX
Opens dampers to exhaust air from pool hall at all times, even in unoccupied mode.
 
MIN
Turns off fresh air fan and closes dampers to minimum position.
 
NOTE
On machines with LPHW, if the optional frost protection stat is fitted, the operation of the 
dampers will be inhibited when the ambient temperature is below 6ºC.
 
 
 
 