SETTING FOR AUTOMATIC OCCUPIED/UNOCCUPIED OPERATION WITH REMOTE INTERFACE
To set for remote control of occupied/unoccupied, slide lever to 'O'. See section 2.4, Note 1 for more information on
remote interface. If the unoccupied period is more than 20 hours per day, extend one segment at 9:00 or other
suitable time that does not coincide with the main occupied period.* Ensure all other segments are pushed in-
wards and slide lever to 'A'.
SETTING FOR MANUAL OCCUPIED/UNOCCUPIED OPERATION
To set for manual occupied period (or override automatic unoccupied period) slide the lever to 'I' for 'occupied'. If
the unoccupied period is more than 20 hour per day, to set for a manual unoccupied period slide the lever to 'O' for
'unoccupied'; extend outwards one segmentat 9:00 or other suitable time that does not coincide with the main
occupied period* and ensure all other segments are pushed inwards.
*In unoccupied mode, the pool water is not heated unless a demand for dehumidification occurs during this period.
If the unoccupied is more than 20 hours per day, it is recommended to allow a brief occupied period to allow the
water temperature to be sampled and maintained if necessary.
3.2.2 WIRING TO EXTERNAL SWIMMING POOL PUMP/FILTER TIME CLOCK
SERIES 3 VARIHEAT.
EXTERNAL COMPONENTS TO
BE WIRED TO TERMINAL
BLOCK LOCATED INSIDE
MACHINE ELECTRIC BOX. SEE
SECTION 2.4
L
9
8
N
Page 28
CUSTOMERS EXTERNAL
PUMP/FILTER TIME CLOCK
POOL PUMP
STARTER
SD437350 ISSUE 22