Relay Output; External 24 V Power Supply; Auxiliary Voltage Terminals Acu Size 8 (160 - SKS Sweden BONFIGLIOLI Vectron ACTIVE CUBE Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4.2.1 Relay output

1 ... 3 Relay output, floating change-over contact, response time approx. 40 ms,

4.2.2 External 24 V power supply

The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage output or voltage input. By
GB
connecting an external power supply of DC 24 V ±10% to terminals X210A.1/X210A.2, the function of inputs
and outputs as well as the communication can be parameterized and maintained, even when mains voltage is
off.
Input voltage range
Rated input current
Peak inrush current
External fuse
Safety
CAUTION
The digital inputs and the DC 24 V terminal of the electronic control equipment can withstand
external voltage up to DC 30 V. Avoid higher voltage levels. Higher voltages may destroy the unit.
4.3
Auxiliary voltage terminals ACU size 8 (160...400 kW)
When using an ACU501 or ACU601 device the connection of 3 x AC 400 V on terminal X13 is necessary.
62
Ter.
maximum contact load:
make contact: AC 5 A / 240 V, DC 5 A (ohmic) / 24 V
break-contact: AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
Requirements to be met by external power supply
DC 24 V ±10%
Max. 1.1 A
Typeically: < 25 A
Via standard fuse elements for rated current, characteristic: slow
Safety extra low voltage (SELV) according to EN 61800-5-1
Control terminal X10
Description
1 ... 6
Not used
7
8
L1
9
L2
10
L3
Connection power
≥ 1,2 kW
Connection voltage
400 V +- 10 %
Connection fre-
50 / 60 Hz
quency
Quick Start Guide ACU
Terminal X13
PE
Connection
02/15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bonfiglioli vectron acu 201Bonfiglioli vectron acu 401

Table des Matières