Commissioning
Commissioning steps
Step
Description
9.
Assign process data output words of the standard device to the
process data input words (PIW) of the master via C1510.
Lenze setting:
PIW10: Ramp function generator input (NSET1−RFG1−IN)
10.
Enable process output data via C1512 = 65535.
l
Only required if C1511 has been changed.
l
Deactivate process data words that are not used by setting the
respective subcode of code C1511 to 0.
l
The value in C1512 is volatile, and all process data are enabled
after every switch−on.
11.
Enable standard device via terminal 28 (CINH).
l
Set terminal 28 to HIGH level.
12.
Enter the setpoint.
l
The master transmits the setpoint via the process data output
word selected.
13.
Change to the READY TO START status:
l
The master transmits the DRIVECOM control word:
0000 0000 0111 1110
14.
The standard device is in the READY TO START status.
l
The master receives the DRIVECOM status word:
xxxx xxxx x01x 0001
15.
Change to the OPERATION ENABLED status.
l
The master transmits DRIVECOM control word:
0000 0000 0111 1111
16.
Now the drive starts up.
62
PIW1: DRIVECOM status word (DRIVECOM STAT)
PIW2: Output frequency with slip (MCTRL1−NOUT+SLIP)
PIW3: Output frequency without slip (MCTRL1−NOUT)
PIW4: Apparent motor current (MCTRL1−IMOT)
PIW5: Actual process controller value (PCTRL1−ACT)
PIW6: Process controller setpoint (PCTRL1−SET1)
PIW7: Process controller output (PCTRL1−OUT)
PIW8: Controller load (MCTRL1−MOUT)
PIW9: DC−bus voltage (MCTRL1−DCVOLT)
(007E
bin
bin
(007F
bin
).
hex
).
hex
l
Detailed
information
PROFIBUS
communication
manual
PROFIBUS
communication
manual
EDK82ZAFPC−001 DE/EN/FR 7.0