COMPLIANCE
SYSTEM CONNECTION
Supply types / number of wires
3x230/400v
management
frequency
SUPPLY
CONSUMPTION
Supply
Current circuit
CURRENT (TRMS)
Starting current (ist)
minimum current (imin)
transition current (itr)
reference current (iref)
Permanent overload (imax)
Short-term over-current
VOLTAGE (TRMS)
direct measurement
Permanent overload
POWERS
Active
reactive
resolution
ENERGY
Active
reactive
total and partial metering
Bidirectional metering (eA+ and eA-)
resolution
interval
Load curve
integration time for load curves
ACCURACY
Active energy
TARIFFS
tariff management
number of tariffs managed
tariff exchange input
METROLOGICAL LED
impulse weight
Colour
DISPLAY
type
refresh time
Back-lighting illumination time
List of functions displayed
* functions available only via communication, the complete list of these functions is given in the down-
loadable m-BUS communication table.
COUNTIS E35 - ref.: 540 683 B
european emC directive no. 2004/108/eC (15/12/2004)
Lv directive no. 2006/95/eC dated 12 december 2006
ieC 62053-21 / ieC 62052-11
Single phase 2 wires 230v
three phase 3 wires 3x230v / 3x400v and three phase 4 wires
detection of cabling error
50 and 60 Hz (± 5 Hz)
Autosupplied
< 10 vA or 2 W
< 2.5 vA
80 mA
0.5 A
2 A
20 A
100 A
3000 A for 10 ms (en50470-3 and ieC 62053-21)
230vAC Phase/neutral 400v AC Phase/Phase ± 15%
230 / 400 v AC + 15%
Yes
no*
0.1 kW
Yes
no*
Yes (0 to 9999999 kWh)
Yes
1 kWh
---
---
---
Class 1 (ieC 62053-21)
Yes*
4*
no*
500 impulses / kWh or 2Wh / impulse
red
7 digit Led with blue back-lighting
1s
30 s
Cf. table below.
C
m
Sp
G
Li
B
en
C
Lo
C
O
St
H
C
d
L
m
C
n
C
n
C
Pr
W
O
R
Su
W
r