From the BMS configuration menu, it is possible to define all the settings
regarding any supervisor connected to the unit that can control operation.
Type of supervisor:
1
NONE (supervision system by the customer. The machine is
supervised, but the supervisor can not be on / off)
SUPERV.GENERICO (supervision system by the customer. The
machine can be supervised and the supervisor can be on / off)
KSMR (KSMR - chiller sequencer)
IRTECH/SYSPDC (KCSI – System controller and IRTECHMASTER)
SIR (SIR – Integrated Sequencer)
EXPBOX
Action to be taken in case of disconnection of the supervisor/sequencer
2
OVERRIDE OFF (THE UNIT SHUTS DOWN)
OVERRIDE ON (the unit bypasses the supervisor and only considers
the display set-up)
NONE (the unit ignores disconnection and continues with the last
command received)
Enable conversion in the event of LonWorks® communication (to be
3
activated only with the KFTT10 board)
Enable conversion in the event of Bacnet® communication (to be activated
4
only with the KBE and KBM board)
Select the variable list to display in supervision
5
NOTE:
for KSMR, KCSI and IrtechMaster set table #0
for SIR and ExpBOX, set table #1
Setting the BMS port of the MASTER board
Setting the Fieldbus port of the MASTER board
Setting the BMS2 port of the MASTER board
Setting the BMS port of the SLAVE board
Setting the Fieldbus port of the SLAVE board
None / HITECSA / MODBUS / WINLOAD / MODBUS EXT
1
1200 / 2400 / 4800 / 9600 / 19200
2
1÷207
3
NONE / EVEN / ODD
4
1 / 2
5
USM_CONTROL EQS_2335a21275_208549_210701_ES-EN-FR-DE-IT
I.4
IMPORTANT!
1
2
3
4
5
The logic with which you view the alarms is as follows:
There are no active alarms still seen
We have already seen active alarms
There have not yet seen past alarms
Detection of an alarm could cause the unit to shutdown automatically.
In order to view the screen showing the type of alarm triggered, press the ALARM
key once.
The logic with which you view the alarms is as follows:
Serious alarm unit
Serious alarm unit or circuit alarm
Serious alarm unit or circuit alarm or
compressor alarm
Serious alarm unit or circuit alarm or
compressor alarm or other alarm
The display will then view one or more of the following screens:
1
2
3
4
5
Type of alarms:
ALXxx
ALBxx
ALCxx
1
ALUxx
2
ALDxx
3
4
ALVxx
5
ALGxx
Reset:
AUTO
SEMIAUTO
1
2
3
MAN
4
SVC
5
To reset a Semiautomatic alarm that has already reached the maximum number
of possible resets or a manual alarm, press the ALARM key for 5 seconds.
1
2
3
4
5
1
2
3
4
5
73
ALARM SIGNALS
Always check the source of the alarms displayed on the unit. Do
not use the unit without having identified and eliminated the
cause of the alarm.
In the event of operating faults, the LED relative to the

ALARM key turns on emitting a red light accompanied by a
continuous acoustic signal.
Beep + led flashing
led fixed
led flashing
Electronic boards disconnection alarms
Disconnected/faulty probe alarms
Circuit/compressor blocking alarms
Unit blocking alarms
Electronic thermostatic valve driver alarms
Warnings
Other general alarms
The alarm is automatically reset when the alarm conditions
cease
The alarm is automatically reset for a maximum number of
times per hour and times per day
User action is required to reset the alarm
Reset alarm reserved to the installer. It is carried out
exclusively in the Service menu
CONTROL EQS
stop the unit
stop the circuit
stop the compressor
led light on display