I.3.4 Menu Restrictions - Hitecsa ADVANCE EQS Mode D'emploi

Commandes électroniques
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Screen B01 allows you to set the clock and to enable the time bands.
Screens B02...B03 can be used to set the daily time bands relative the cooling
mode.
3
Date to be programmed. By changing the day, the time bands of the selected
1
day will be shown on the display.
The displayed day set can be copied on another day at will. Select the
2
destination day and then set YES.
Setting the starting time of the time period. The band ends with the start of the
3
following band or at the end of the work day. Warning: it is required to insert
times in an increasing order for correct operation of the time bands.
Primary side control settings. For each band, you can set an OFF command,
4
a switch on command with SET1 or switch on with SET2 (with DSP option
only).
Recovery side control settings. For each band, you can set an OFF
5
command, a switch on command with SET1 or switch on with SET2 (with
DSP option only). (only EXP or HP+RC100 versions)
With the parameters set in the example screen:
time period 1 begins at 8:30 and ends at 17:00;
time period 2 begins at 17:00 and ends at 23:59
Before 8:30, as there is no indication, the command at the end of the day is used
(in this case OFF)
Screen B03 can be used to set the "special periods" the commands of which have
a priority with respect to the daily time bands. During these periods, the settings of
the daily time bands do not apply.
1
Starting date of special period
1
End date of special period
2
Primary side control settings. For each band, you can set an OFF
3
command, a switch on command with SET1 or switch on with SET2 (with
DSP option only).
Recovery side control settings. For each band, you can set an OFF
4
command, a switch on command with SET1 or switch on with SET2 (with
DSP option only). (only EXP or HP+RC100 versions)
With the parameters set in the example screen, the unit will be kept turned off
from December 1 until 31, regardless of any previous orders.
Screen B04 can be used to set the "special days" the commands of which have a
priority with respect to the special periods. During these periods, the settings of
the special periods or of the daily time bands do not apply.
1
Special day
1
Primary side control settings. For each band, you can set an OFF
2
command, a switch on command with SET1 or switch on with SET2 (with
DSP option only).
Recovery side control settings. For each band, you can set an OFF
3
command, a switch on command with SET1 or switch on with SET2 (with
DSP option only). (only EXP or HP+RC100 versions)
Only for EXP or HP versions there are identical screens to the previous ones, to
set the time bands in heating or SELECT mode.
USM_CONTROL EQS_2335a21275_208549_210701_ES-EN-FR-DE-IT
1
2
4
5
2
3
4
2
3
I.3.4
Menu Restrictions
In the Restrictions menu it is possible to define the use of the FDL (Power
Reduction) option, with which to limit the power output of the machine and
consequently its input, and of the FNR (Noise Reduction) function, with which to
limit the noise generated by fans editing the ventilation control settings. The FDL
and FNR options are factory enabled.
I.3.4.1
Power reduction (FDL accessory)
Sources of the power reduction command
1
Percentage value referred to the total machine power to which the power
demand is limited
The EEM accessory enables you to set a % value of the maximum power or
maximum kW absorbed.
The possible sources of the power reduction command are:
Function disabled
DISABLED
Function active for time periods
T.BAND
Function active for digital input (open contact function
DIN
disabled, closed contact function enabled)
Function active for digital input or for time periods
DIN+F. HOURLY
Function is always enabled
Always
If the FDL function is activated from TIME BAND or DIN+TIME BAND, in the
following screen you can set the daily bands for cooling mode:
Date to be programmed. By changing the day, the time bands of the selected
1
day will be shown on the display.
The displayed day set can be copied on another day at will. Select the
2
destination day and then set YES.
Setting the starting time of the time period. The band ends with the start of the
3
following band or at the end of the work day. Warning: it is required to insert
times in an increasing order for correct operation of the time bands.
For each band it is possible to set an OFF command (FDL disabled), or FDL
4
enabled.
With the parameters set in the example screen:
Band 1 starts at 01:00 and ends at 07:00 (FDL activated).
Band 2 starts at 07:00 and ends at 22:00 (FDL deactivated)
Band 3 starts at 22:00 and ends at 23:59 (FDL activated)
Before 1:00, since there is no indication, it executes the last command set the
previous day.
Only for EXP or HP versions there is an identical screen to the previous one, to
set the time bands in heating or SELECT mode.
70
CONTROL EQS
1
2
1
2
3
4

Publicité

Table des Matières
loading

Table des Matières