Iii Section Iii: Assistance; Menu Navigation; Hour Meter Menu; Probe Calibration Menu - Hitecsa ADVANCE EQS Mode D'emploi

Commandes électroniques
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

III SECTION III: ASSISTANCE

IMPORTANT!
The use of this menu is only allowed for qualified personnel that
can use it by entering the correct password.
From the main menu, keeping the Prg key pressed for 5 seconds displays the
screen for entering the password to access the screens reserved for the installer.
In order to obtain the installer password, please contact HITECSA.
Enter the right password to display menu J. Assistance.
USM_CONTROL EQS_2335a21275_208549_210701_ES-EN-FR-DE-IT
III.1

MENU NAVIGATION

In the Assistance menu, you can change sensitive parameters of the unit that
determine its behaviour and govern all the software functions. The Assistance
menu is subdivided into sub-menus
Press the PRG key to access the main menu. With the UP and DOWN keys the
desired menu can be selected, by successively pressing the Enter key, access is
allowed. Press the Esc key to return to the previous menu.
III.1.1

Hour meter menu

In the Hour Counter Setting menu it is possible to edit the counters of the hours
worked and switch-ons performed by each fan, in addition to managing the
required maintenance alarm.
In windows Ja01 and subsequent it is possible to edit the number of total work
hours performed by each compressor, as well as the number of switch-ons
performed.
In menu Ja05 it is possible to edit the threshold of work hours that triggers the
"maintenance required" alarm. It is also possible to reset the triggered alarm and
reset to zero the hour counter that triggers the alarm.
III.1.2

Probe calibration menu

Corrections to the readings of the probes may be made in the Probe calibration
menu.
Sampling range for the average calculation of the outdoor air temperature
1
(mobile average on 10 samples)
Enable external air temperature probe
2
The reading correction for each probe may be made in screens Jb01 and
following, and the resulting value is displayed
81
CONTROL EQS
1
2
correction
resulting value
correction
resulting value

Publicité

Table des Matières
loading

Table des Matières