Heating mode settings
Main set-point in HEATING/SELECT mode
1
Secondary set-point in HEATING/SELECT mode (only with DSP option)
2
Correction applied to set-point with CS function in Offset mode (only with
3
CS option)
Set-point display of actual work
4
Recovery mode settings (only EXP or HP+RC100 versions)
Main set-point in recovery mode
1
Secondary set-point in recovery mode (only with DSP option)
2
Correction applied to set-point with CS function in Offset mode (only with
3
CS option)
Set-point display of actual work
4
I.3.2.5
Set-point Compensation
If the machine is regulated to return temperature or flow temperature with AF+
used in Precision mode, you can enable set-point climatic compensation
according to the outdoor temperature. The less the outdoor conditions are severe,
the higher the set-point correction applied. Compensation can be
enabled/disabled individually for each operating mode.
Cooling mode settings
Enable set-point climatic compensation
1
Maximum compensation applied to set-point (*)
2
Outdoor temperature threshold over which no compensation is applied (**)
3
Outdoor temperature band along which set-point gradual compensation is
4
applied. (***)
Set-point climate compensation graphic in cooling mode
Set-point
T
Outdoor temperature
Te
Maximum compensation
(*) Max.C
Outdoor temperature differential
(**) DtE
Outdoor temperature set-point
(***) StE
Example: The Set-point is not changed with parameters set in the sample screen
over 25°C outdoor temperature; for a colder temperature, it is progressively
increased up to a maximum increase of 5°C for outdoor temperatures up to 15°C.
USM_CONTROL EQS_2335a21275_208549_210701_ES-EN-FR-DE-IT
Heating mode settings
1
2
3
4
1
2
3
4
1
2
3
4
Example: The Set-point is not changed with parameters set in the sample screen
below 5°C outdoor temperature; for a warmer temperature, it is progressively
decreased to a maximum decrease of 5°C for outdoor temperatures exceeding
1
35°C.
2
3
Recovery mode settings (only EXP or HP+RC100 versions)
4
1
2
3
4
1
2
3
68
Enable set-point climatic compensation
Maximum compensation applied to set-point (*)
Outdoor temperature threshold below which no compensation is applied (**)
Outdoor temperature band along which set-point gradual compensation is
applied. (***)
Set-point climate compensation graphic in heating mode
Set-point
T
Outdoor temperature
Te
Maximum compensation
(*) Max.C
Outdoor temperature differential
(**) DtE
Outdoor temperature set-point
(***) StE
Enable set-point climatic compensation
Maximum compensation applied to set-point
Outdoor temperature threshold beyond which no compensation is applied
Outdoor temperature band along which set-point gradual compensation is
applied
I.3.2.6
Machine settings (only EXP or HP+RC100
versions)
In SELECT operation indicates the side (primary or recovery) to be
prioritised if there are simultaneous requests
In SELECT operation if the evaporator input temperature is lower than the
set threshold, it forces priority in PRIMARY (PDC+RC100 only).
In SELECT operation, if the evaporator input temperature is higher than the
set threshold + differential, it goes back to set priority (PDC+RC100 only).
CONTROL EQS
1
2
3
4
1
2
3
4
1
2
3