CLIVET DUCT-SM 2 Mode D'emploi page 84

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

REMOTE ON-OFF
For the input of the remote control terminal CN23 (ON-
OFF) and the JR6 quick-release connector
– Remove the JR6 quick-release connector when
using the ON-OFF function;
– When the remote switch is OFF (OPEN), the unit
will be turned off;
– When the remote switch is ON (CLOSE), the unit
will be turned on;
– When the remote switch is opened/closed, the unit
will respond to the request within 2 seconds;
– When the remote switch is ON, the remote/wired
control can be used to select the mode; when the
remote switch is OFF, the unit will not respond to
the remote/wired control request.
When the remote switch is OFF, the remote/wired
control is on, code CP will be shown on the display
board.
– The input voltage is 12 V DC, the maximum design
current is 5 mA.
32
ALARM
For the input of ALARM connector CN33
Fig. 41
– The terminal input is set up for ALARM connection,
but there is no voltage; the power supply comes
from the ALARM system (not from the unit)
– Although the design voltage can withstand even
higher values, we strongly advise connecting a
power supply of less than 24 V and a current of
less than 0.5 A
– If this problem occurs on the unit, the relay will be
closed, thus activating the ALARM
OUTDOOR AIR FAN
For the input of terminal CN43 of the new outdoor air
motor.
– Connect the fan motor to the input, regardless of
the motor's L/N;
– The output voltage is the power supply;
– The outdoor air motor cannot exceed 200 W or 1A;
choose the lower value;
– The new outdoor air motor will start when the
internal fan motor is running; when this motor
stops, the outdoor air motor also stops;
– When the unit goes into forced cooling mode or
power test mode, the outdoor air motor will not
work.
Installation
Fig. 42
Fig. 43

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Duct-sl 2

Table des Matières