Installation
d
It is PROHIBITED to install the indoor
unit in the following locations:
– in a bathroom or laundry room, because
excess humidity can reduce its service life
and corrode the cables;
– near sources of heat, steam or combustible
gas;
– near flammable objects, such as curtains or
fabrics;
– near obstacles that could obstruct air
circulation;
– near the entrance;
– In an area that is not exposed to direct
sunlight;
– areas exposed to strong electromagnetic
waves;
Please refer to the following diagram for wall and ceiling distances:
Strong and resistant ceiling
Left side
>10 cm
Space for maintenance
≥20 cm
indoor unit
>30 cm
Air outlet
Air inlet
d
It is PROHIBITED to install the indoor
unit in the following locations:
– oil extraction drilling or fracking areas;
– coastal areas with extremely salty air;
– areas with an atmosphere impregnated with
caustic gases, for example near thermal
sources;
– areas subject to strong power fluctuations,
for example factories;
– enclosed spaces (cabinets, etc.);
– kitchens with natural gas cooker hobs;
– areas used for storing gas or flammable
materials.
>2 cm
>2 cm
Access for
maintenance
Floor
60cm x 60cm
Inspection opening
>30 cm
Ceiling
≥30 cm
Fig. 3
11