Efficiency
Overload capacity
Number of output phases
Batteries and battery charger characteristics
Number of batteries
Battery type
Unitary capacity
Rated Battery Voltage
Backup time with 50%
linear load
Battery extension
Maximum charge current
Recharge time (to 90%)
Communication and management
Screen and signalling
Communications ports
Software
Protections
Mechanical characteristics
Dimensions W x H x D( mm)
5 kVA - 6 kVA - 10 kVA
3 101 73
up to 94%
105% continuous
120% for 30 seconds
150% for 10 seconds
Single phase
Lead-acid sealed without maintenance (VRLA)
12 Vdc - 5 Ah
240 Vdc
> 5 min
1.86 A
4 hours
six pushbuttons and four LEDs for
real-time control of the status and
the main parameters of the UPS
RS232 and USB
Connector for network interface
Software for Windows and Linux
environments is available in order to:
- displaying all the functioning and
diagnostic data in case of problems;
- setup of special functions.
Download a copy free of charge from the
website http://www.ups.legrand.com
Electronic circuits against overloads
and short-circuit
Backfeed
Emergency Power Off (EPO)
Overtemperature
440 x 176 (4U) x 680
DAKER DK Plus
3 101 74
20
Yes