Installation instructions
Warning
Use only power units which guarantee reliable isolation
of the operating voltages as per IEC 742/EN 60742/
VDE 0551 with at least 4 kV isolation resistance (Pro
tected Extra Low Voltage PELV). Switch power packs are
permitted, providing they guarantee reliable isolation
in accordance with EN 60950/VDE 0805.
By the use of PELV power units, protection against electric
shock (protection against direct and indirect contact) is
guaranteed in accordance with EN 60204−1/IEC 204.
Safety transformers with the adjacent symbol must be
used for supplying PELV networks. The module must be
earthed to ensure that it functions correctly (e.g. EMC).
Pin assignment of sensor plug (connection SIGNALS,
X31)
1
LIM+: limit switch
positive
2
REF: reference
switch
3
LIM−: limit switch
negative
4
24 V: supply
5
GND: supply
Connection
cross−sectional
area max. 1.5 mm
Festo SPC200−SMX−1 0309a English
2
1
2
3
4
5