This solution is recommended when you want to enter a reserved area in both directions by activating a command (radio control, proximity
key, magnetic keys, etc.).
ENTRY
EXIT
Loops S1 and S2 also have a safety function in that they will not let the bollard to move all the time if the vehicle is over S1 or S2.
RECOMMENDED
DIMENSIONS
- Connect the N.O. contact of the coil S1 and S2 receiver to
PDM input.
- The dimensional values given are approximate.
*
We suggest installing the "MAK-2" metal mass detector.
Control unit
INSTALLATION C
13.3
CONTROLLED ENTRY AND EXIT
PARAMETER
DATA
- 39 -
The vehicle approaches the reserved
area.
When the vehicle is over loop S1
the bollard will go down only after a
command (ex.: remote control).
If the device is rising and the user
wants to lower it again, the vehicle
must be over loop S1 and the com-
mand must be repeated.
When the vehicle is no longer over
loop S2, the bollard will go up
automatically after an adjustable
pause time.
The vehicle approaches the reserved
area.
When the vehicle is over loop S2,
the bollard will go down only after a
command (ex.: remote control).
If the bollard is rising and the user
wants to lower it again, the vehicle
must be over loop S2 and the com-
mand must be repeated.
When the vehicle leaves
loop S1 the bollard will
rise automatically af-
ter an adjustable pause
time.
DESCRIPTION
Functioning logic: Automatic
Pause time
Opening consent and pause time reset
Radio channel 1: Open
Command during pause is OFF
Standard close
EN