Masquer les pouces Voir aussi pour PLATIN XXL 20.000:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

PLATIN XXL Löschwasserbehälter
DE
Einbau-/ Montage-/ und Wartungsanleitung für
PLATIN XXL Löschwasserbehälter
>> Seite 1-14
EN
Installation and maintenance instructions for
PLATIN XXL extinguishing water tank
>> Page 15-28
Notice d'installation et d'entretien Platine XXL
FR
GRAF Réserve Incendie
>> Page 29-42
ES
Instrucciones para montaje y mantenimiento del
GRAF PLATIN XXL depósito de agua para extinción de incendios
>> Página 43-56

Publicité

Table des Matières
loading

Sommaire des Matières pour Graf PLATIN XXL 20.000

  • Page 1 Installation and maintenance instructions for PLATIN XXL extinguishing water tank >> Page 15-28 Notice d’installation et d’entretien Platine XXL GRAF Réserve Incendie >> Page 29-42 Instrucciones para montaje y mantenimiento del GRAF PLATIN XXL depósito de agua para extinción de incendios >> Página 43-56...
  • Page 2: Table Des Matières

    Einbau-/ Montage-/ und Wartungsanleitung für PLATIN XXL Löschwasserbehälter PLATIN XXL 20.000 - 65.000 Liter Bestellnummer: 20000 L: 391400 (391810+371018+371065) 25000 L: 391401 (391811+371018+371065) 30000 L: 391402 (391812+371018+371065) 35000 L: 391403 (391813+371018+371065) 40000 L: 391404 (391814+371018+371065) 45000 L: 391405...
  • Page 3: Allgemeine Hinweise

    (Teleskop-Domschacht entsprechender Abdeckung)! Es sind nur Original GRAF – Abdeckungen oder von Fa. GRAF schriftlich freigegebene Abdeckungen zu verwenden. Die Firma GRAF bietet ein umfangreiches Sortiment an Zubehörteilen, die alle aufeinander abgestimmt sind und zu kompletten Systemen ausgebaut werden können. Die Verwendung, nicht von GRAF freigegebener Zubehörteile führt zu einem Ausschluss der Gewährleistung/Garantie.
  • Page 4: Einbaubedingungen

    Einbaubedingungen Teleskop-Domschacht LKW Teleskop-Domschacht Maxi + (Abdeckung nach DIN 3223 – Teleskop-Domschacht Guss Überdeckungshöhen mit Teleskop Domschacht bauseits zu stellen) Teleskop-Domschacht Mini LKW (Abdeckung nach DIN 3223 - bauseits zu 750 – 1050 mm 750 - stellen) im begehbaren Grünbereich 750-1050 950/1050 Maximale Überdeckungshöhe mit Zwischenstück...
  • Page 5: Technische Daten

    Technische Daten Technische Daten Platin XXL Tankübersicht Platin XXL Tank 20.000 L 25.000 L 30.000 L 35.000 L 40.000 L Art.-Nr. 391400 391401 391402 391403 391404 Gewicht 890 kg 1105 kg 1355 kg 1570 kg 1750 kg 9405 mm...
  • Page 6 Technische Daten Löschwasser Ausbau- komponenten Bezeichnung Material PE/ V2A Gewicht (kg) 11,5 13,5 Ø (mm) DN 125 DN 125 DN 125 DN 110 Pfosten: 40 L (mm) Halter: 250 Pfosten: 40 B (mm) Halter: 200 H (mm) 1200...
  • Page 7: Aufbau Tank

    Aufbau Tank Teleskop-Domschacht LKW (Abdeckung nach DIN 3223 – bauseits zu stellen) Profildichtung Tankdom/ Teleskop Tankdom (um 360° drehbar) Profildichtung Tank/ Tankdom Platin XXL Löschwasserbehälter Sauganschluss mit A-Festkupplung nach DIN 14244 Verlängerungsstück für Saugrohr mit Flansch DN 125 Saugrohr mit Flansch DN 125 inkl.
  • Page 8: Einbauort

    Einbau und Montage Einbauort Die Löschwasserentnahmestelle muss sich außerhalb des Trümmerschattens von Gebäuden befinden. Zur Entnahmestelle ist von der öffentlichen Verkehrsfläche eine Feuerwehrzufahrt zu erstellen. Die Zufahrt muss den Anforderungen nach DIN 12090 entsprechen, sofern landesrechtliche Vorgaben dem nicht entgegenstehen.
  • Page 9: Verbindung Mehrerer Behälter

    über die Montageflächen mittels GRAF- 600 mm Spezialdichtungen und KG-Rohren (bauseits zu stellen). Die Öffnungen sind ausschließlich mit dem GRAF- Spezialkronenbohrer in der entsprechenden Größe zu bohren. Es ist darauf zu achten, dass der Abstand zwischen den Behältern mind. 600 mm beträgt. Die Rohre...
  • Page 10: Einsetzen Und Verfüllen

    Einbau und Montage Einsetzen und Verfüllen Die Behälter sind stoßfrei mit geeignetem Gerät vorbereitete Baugrube einzubringen. Um Verformungen zu vermeiden wird der 2. 3/3 Behälter Anfüllen 1. 1/3 1. 1/3 Behälterumhüllung zu 1/3 mit Wasser gefüllt, danach wird die Umhüllung (Rundkornkies max.
  • Page 11: Montage Tankdom Und Teleskop-Domschacht

    Montage Tankdom und Teleskop-Domschacht Tankdom montieren Vor der eigentlichen Montage wird mitgelieferte Dichtung zwischen Tank und Tankdom auf Aufnahmeprofil Tankhalses „B“ geschoben. Anschließend wird der Tankdom den Leitungen nach ausgerichtet und bis zum Anschlag in den Tankhals eingeschoben. Es muss unbedingt auf den Sitz der oberen Dichtung „A“...
  • Page 12: Teleskop - Domschacht Pkw Befahrbar

    Montage Tankdom und Teleskop-Domschacht Teleskop – Domschacht PKW befahrbar Wird der Behälter unter PKW befahrenen Flächen installiert muss das Teleskop (Farbe Anthrazit) im Kragenbereich mit Beton (Belastungsklasse B25 = 250 Kg/ m²) unterfüttert werden. Die anzufüllende Betonschicht muss umlaufend mind.
  • Page 13: Montage Zwischenstück

    Montage Zwischenstück Zwischenstück montieren Wird bei größeren Erdüberdeckungen ein Zwischenstück benötigt wird dieses unter Zuhilfenahme von Schmierseife in den Tankdom eingesetzt. In die oberste Nut des Zwischenstücks wird die Profildichtung eingelegt und großzügig eingefettet. Anschließend den Teleskop-Domschacht einschieben und an die geplante Geländeoberfläche anpassen.
  • Page 14: Löschwasser Ausbaukomponenten

    Löschwasser Ausbaukomponenten Saugarmatur Das Saugrohr hat einen Innendurchmesser von 125 mm und wird standardmäßig mit dem, sich im Lieferumfang enthaltenen, Löschwasser-Sauganschluss nach 14244 A-Festkupplung verschraubt. Zur Flanschabdichtung bitte beiliegende Dichtscheibe mit Stahleinlage verwenden! Die Dichtflächen sind sauber, trocken und parallel ausgerichtet vorzubereiten und die Flanschverbindungen im Anschluss mit den jeweiligen Schraubensätzen, in mehreren Durchgängen...
  • Page 15: Inspektion Und Wartung

    Inspektion und Wartung Die gesamte Anlage ist mind. alle drei Monate auf Dichtheit, Sauberkeit und Standsicherheit zu überprüfen. Eine Wartung der gesamten Anlage sollte in Abständen von ca. 5 Jahren erfolgen. Dabei sind alle Anlagenteile zu reinigen und auf ihre Funktion zu überprüfen, sodass eine einwandfreie Löschwasserentnahme jederzeit gewährleitet ist.
  • Page 16 Installation and maintenance instructions for PLATIN XXL extinguishing water tank PLATIN XXL 20.000 - 65.000 l Order No.: 20000 l: 391400 (391810+371018+371065) 25000 l: 391401 (391811+371018+371065) 30000 l: 391402 (391812+371018+371065) 35000 l: 391403 (391813+371018+371065) 40000 l: 391404 (391814+371018+371065)
  • Page 17: General Notes

    Only original GRAF covers or covers approved in writing by GRAF must be used. GRAF offers an extensive range of accessories, all of which are designed to match each other and which can be extended to form complete systems. The use of accessories that have not been approved by GRAF results in the exclusion of the warranty/guarantee.
  • Page 18: Installation Conditions

    Installation conditions Teleskop-Domschacht Telescopic lorry dome shaft (cover in Maxi + accordance with DIN 3223 - to be Teleskop-Domschacht Guss provided by the customer) Teleskop-Domschacht Covering heights with telescopic lorry dome shaft Mini (cover in accordance with DIN 3223 - to be 750 –...
  • Page 19: Technical Data

    Technical data Technical Data Platin XXL Overview tanks Platin XXL Tank 20.000 L 25.000 L 30.000 L 35.000 L 40.000 L Art. No. 391400 391401 391402 391403 391404 Weight 890 kg 1105 kg 1355 kg 1570 kg 1750 kg...
  • Page 20 Technical data Extinguishing water removal components Description Material PE/ V2A Weight (kg) 11.5 13.5 Diameter DN 125 DN 125 DN 125 DN 110 (mm) Post: 40 L (mm) Holder: 250 Post: 40 W (mm) Holder: 200 H (mm)
  • Page 21: Tank Structure

    Tank structure Telescopic lorry dome shaft (cover in accordance with DIN 3223 - to be provided by the customer) Profile seal of tank dome / telescope Tank dome (can be rotated 360°) Profile seal of tank / tank dome...
  • Page 22: Installation Site

    Installation and assembly Installation site The extinguishing water extraction point must be outside the debris zone of buildings. Access for the fire brigade should be provided to the extraction point from the public road. The access route must meet the requirements of DIN 12090 provided these don't contradict local requirements.
  • Page 23 (to be provided at construction site). The apertures must be drilled to the corresponding size using only the GRAF special crown bit. It must be ensured that the distance between the tanks is at least 600 mm. The pipes must project at least...
  • Page 24: Insertion And Filling

    Installation and assembly Insertion and filling The tanks must be inserted, impact-free, into prepared trench using suitable equipment. To avoid deformities, the tank is filled 1/3 with water before filling in the tank surrounding. 2. 3/3 1. 1/3 1.
  • Page 25: Assembling The Tank Dome Telescopic Dome Shaft

    Assembling the tank dome telescopic dome shaft Assembling the tank dome Prior assembly, the enclosed seal is locked onto the tank neck’s profile „B“. The tank dome is then locked to the tank neck. It is essential to make sure that the upper seal "A"...
  • Page 26: Assembling The Tank Dome And Telescopic Dome Shaft

    Assembling the tank dome and telescopic dome shaft Telescopic dome shaft over which passenger cars may drive If the tank is installed under areas used by passenger cars, the collar area of the telescope (colour anthracite) must be supported with concrete (load class B25 = 250 kg/ m²).
  • Page 27: Assembly Of The Adapter

    Assembly of the adapter Assembling the extension For larger coverage heights an extension is needed. To insert the extension into the tank dome, soft soap is needed. Into the highest groove of the extension the profile seal is inserted an greased generously.
  • Page 28: Extinguishing Water Removal Components

    Extinguishing water removal components Intake device The intake pipe has an inner diameter of 125 mm and as standard is screwed down to the extinguishing water suction connection provided in the scope of supply in accordance with DIN 14244 by means of an A fixed coupling.
  • Page 29: Inspection And Servicing

    Inspection and servicing The entire system must be checked for tightness, cleanliness and stability at least once every three months. The entire system should be maintained approximately every 5 years. This involves cleaning all system parts and checking that they are functioning correctly so that extinguishing water can be easily extracted at all times.
  • Page 30 Notice d’installation et d‘entretien Platine XXL GRAF Réserve Incendie PLATINE XXL 20.000 - 65.000 L Réf.: 20000 L: 391400 (391810+371018+371065) 25000 L: 391401 (391811+371018+371065) 30000 L: 391402 (391812+371018+371065) 35000 L: 391403 (391813+371018+371065) 40000 L: 391404 (391814+371018+371065) 45000 L: 391405...
  • Page 31: Généralités

    (de type coffret d’alimentation GRAF) prévoyant en sécurité une disconnexion entre les deux réseaux et un trop-plein. La société GRAF vous propose une large gamme d’accessoires compatibles avec la cuve. GRAF décline toute prise en charge sous garantie en cas d’utilisation d’accessoires non conformes.
  • Page 32: Installation

    Installation Teleskop-Domschacht Rehausse télescopique en fonte Maxi + Teleskop-Domschacht Guss Teleskop-Domschacht Hauteurs de recouvrement avec dôme et Mini rehausse télescopique comprise entre 750 – 1050 mm 750 - 950/1050 750mm – 1050mm pour un passage piétons Hauteur de recouvrement maximale avec dôme max.
  • Page 33: Données Techniques

    Données techniques Données techniques Platine XXL Vue d’ensemble cuve Platine XXL Volume 20.000 L 25.000 L 30.000 L 35.000 L 40.000 L de cuve Réf. 391400 391401 391402 391403 391404 Poids 890 kg 1105 kg 1355 kg 1570 kg...
  • Page 34 Données techniques Accessoires Réserve Incendie Designation Matières PE/ V2A Poids (kg) 11,5 13,5 Ø (mm) DN 110 DN 125 DN 125 DN 110 Support: 40 L (mm) Plaque: 250 Support: 40 l (mm) Plaque: 200 H (mm) 1200...
  • Page 35: Montage De La Cuve

    Montage de la cuve Rehausse télescopique passage camoins (anneau et couvercle – non fournis) Joint à lèvres EDPM Dôme (pivotant à 360°) Joint à lèvres EDPM Réserve Incendie Platine XXL Raccord pompier DN110 avec bride d‘accouplement Rallonge pour colonne d‘aspiration DN Colonne d‘aspiration DN 125 avec...
  • Page 36: Emplacement

    Installation de la cuve Emplacement L’emplacement du réservoir incendie doit répondre aux directives des autorités. L’accès et le passage doivent être accessibles aux engins de lutte contre l’incendie. Hauteur de remblai La hauteur de recouvrement avec rehausse télescopique passage camions est de 750mm à 1500mm max avec rallonges.
  • Page 37: Nappe Phréatique Et Terrain Argileux

    à l’emplacement prévue à cet effet et à 600 mm l’aide des joints à lèvre spéciaux GRAF. Le perçage des cuves doit être réalisé avec la scie- cloche GRAF. La distance entre deux cuves doit être au minimum de 600 mm.
  • Page 38: Mise En Place Et Remplissage

    Installation de la cuve Mise en place et remplissage Les cuves doivent être installées dans la tranchée grâce à un matériel adapté. L’espace entre la tranchée et la cuve doit être au minimum de 100 mm. 2. 3/3 Remplir d’eau 1/3 de la cuve avant de...
  • Page 39: Montage Du Dome Et De La Rehausse Telescopique

    Montage du dôme et de la rehausse télescopique Montage du dôme Placer les joints d’étanchéité livrés avec le dôme et le couvercle étanche dans les profils des trous d’homme de la cuve (B). Le dôme est orientable selon les arrivées de tuyaux.
  • Page 40 200 mm de hauteur. La hauteur de remblai au-dessus de la cuve est d’au moins 750 mm et 1300 mm max. avec la rallonge GRAF. Le couvercle doit pouvoir s’ouvrir avec une clé à hydrant Rehausse télescopique – passage véhicules >3.5T Dans le cas d’une installation avec anneau et couvercle béton ou...
  • Page 41: Montage De La Rallonge

    Montage de la rallonge Montage de la rallonge Pour un remblai plus conséquent, il est nécessaire d’utiliser une rallonge. Badigeonner la de graisse puis insérer la dans le dôme. Insérer le joint profilé, livré avec la rallonge, dans la rainure du haut de la rallonge après l’avoir préalablement enduit de graisse.
  • Page 42: Equipement Incendie

    Equipement incendie Raccordement d’aspiration La colonne d’aspiration est livrée en DN125 et se réduit en DN110 au niveau du raccord pompier (hydrant) grâce à une bride d’accouplement. Utilisez les brides livrées pour assurer l’étanchéité. Les surfaces d’étanchéité doivent être propres et sèches de part et d’autre des raccords, disposez les face à...
  • Page 43: Vérification Et Entretetien

    Vérification et entretetien L’étanchéité, la propreté et la stabilité de l’ensemble de l’installation doivent être vérifiées au moins tous les trois mois. L’entretien de l’ensemble de l’installation doit être effectué environ tous les 5 ans. Tous les accessoires doivent être nettoyés et vérifiés.
  • Page 44 Instrucciones para montaje y mantenimiento del GRAF PLATIN XXL depósito de agua para extinción de incendios PLATIN XXL 20.000 - 65.000 L Nº pedido: 20000 L: 391400 (391810+371018+371065) 25000 L: 391401 (391811+371018+371065) 30000 L: 391402 (391812+371018+371065) 35000 L: 391403...
  • Page 45: Indicaciones Generales

    Se deben usar exclusivamente cubiertas originales de GRAF o bien cubiertas cuyo uso ha sido autorizado por escrito por GRAF. La compañía GRAF ofrece un amplio surtido de accesorios que han sido adaptados entre sí y que pueden ampliarse para formar sistemas completos. El uso de accesorios no aprobados por GRAF da lugar a la pérdida de la garantía legal/comercial.
  • Page 46: Condiciones De Instalación

    Condiciones de instalación Cubierta telescópica para camiones Teleskop-Domschacht Maxi + (cobertura según DIN 3223 – debe ser Teleskop-Domschacht Guss instalada por el cliente) Teleskop-Domschacht Altura de cobertura con la cubierta telescópica Mini para camiones (cobertura según DIN 3223 –...
  • Page 47: Datos Técnicos

    Datos técnicos Datos técnicos Platin XXL Sobrevista tanques Platin XXL Tanque 20.000 L 25.000 L 30.000 L 35.000 L 40.000 L Nº pedido 391400 391401 391402 391403 391404 Peso 890 kg 1105 kg 1355 kg 1570 kg 1750 kg...
  • Page 48 Datos técnicos Pack de extensión para agua para extinción de incendios Denominación Material PE/ V2A Peso (kg) 11,5 13,5 Ø (mm) DN 125 DN 125 DN 125 DN 110 Poste: 40 Longitud (mm) Soporte: 250 Poste: 40 Anchura (mm)
  • Page 49: Componentes Del Depósito

    Componentes del depósito Cubierta teléscopica transitable para camiones (cubierta según DIN 3223 – debe ser instalada por el cliente) Junta perfilada unión cúpula – cubierta telescópica Cúpula para depósito (girable en 360°) Junta perfilada depósito/ cúpula Platin XXL depósito de agua para extinción de incendios...
  • Page 50: Lugar De Colocación

    Instalación y montaje Lugar de colocación El punto de extracción de agua para extinción de incendios debe situarse fuera del área de caída de escombros. La autoridad con competencia para las superficies de tránsito público debe construir un acceso hasta el punto de extracción del agua para extinción de incendios.
  • Page 51: Conexión De Varios Depósitos

    600 mm especiales de la marca GRAF y tubos de desagüe de canal (a disponer por parte del cliente). Las aberturas deben perforarse exclusivamente con brocas de corona especiales de la marca GRAF con el tamaño correspondiente.
  • Page 52: Colocación Y Relleno

    Instalación y montaje Colocación y relleno Cubra el interior de la zanja excavada con una base de grava. La grava debe ser redondeada con un máximo de granulación del 8/16. No se podrán utilizar elementos punzantes. Nunca depositar desechos obra.
  • Page 53: Montaje De La Cúpula Y Cubierta Telescópica

    Montaje de la cúpula y cubierta telescópica Montaje de la cúpula Primero de todo colocamos la junta entre la cúpula y el tanque. Las alas de la junta tienen que quedar en la cara interior del tanque. Es importante colocar la junta entre la cúpula y la cubierta...
  • Page 54: Cubierta Telescópica Transitable Por Coches

    Montaje de la cúpula y cubierta telescópica Cubierta telescópica transitable por coches En caso de instalar el tanque por debajo de superficies transitadas por coches, debe cubrirse la base de la cubierta con hormigón (B25 = 250 Kg/ m²). La capa de hormigón debe tener un ancho mínimo de 300 mm y una altura de 200...
  • Page 55: Montaje De La Extensión

    Montaje de la extensión Montaje de la extensión (cuando ésta sea necesaria) Introduzca la junta correspondiente (incluida en el envío) en la parte superior de la extensión usando el líquido lubricante. Asegúrese de que la junta está bien colocada. Lubrique la junta superior de la cúpula para facilitar la introducción de la extensión.
  • Page 56: Pack De Extensión Para Agua Para Extinción De Incendios

    Pack de extensión para agua para extinción de incendios Accesorios de aspiración El tubo de aspiración tiene un diámetro interior de 125 mm y se enrosca como estándar con el racor de aspiración para agua de extinción de incendios incluido en el volumen de suministro según DIN 14244 con acoplamiento fijo A.
  • Page 57: Inspección Y Mantenimiento

    Inspección y mantenimiento Comprobar la estanqueidad, limpieza y estabilidad de la instalación en su conjunto, como mínimo cada tres meses. Realizar el mantenimiento de la instalación completa con una periodicidad de aprox. 5 años. El mantenimiento consistirá en la limpieza de todos los componentes de la instalación y en la comprobación de su correcto funcionamiento para garantizar en todo momento la extracción sin...
  • Page 58 Notizen / Notes / Notas...
  • Page 60 © Otto Graf GmbH/963110...

Table des Matières