7. Preventive Maintenance
Tripp Lite SRCOOL33K QUARTERLY MAINTENANCE CHECKLIST
Prepared By: __________________________________________________________________Date:______________________________________
Model Number_________________________________________________Serial Number______________________________________________
Perform all Monthly Maintenance Checklist tasks PLUS the following tasks:
Mechanical/Electrical Inspection
Caution!
Turn off the cooling unit and disconnect all power sources before performing mechanical and electrical checks.
q Inspect fan hardware and tighten if necessary.
q Inspect water pump.
q Clean or replace filters.
q Clean condensate pans.
q Clean the condensate drain line.
q Remove any debris from condensate floats.
q Clean dust from door perforations.
q Clean dust from fan bezels.
q Verify proper functioning of the cooling operation mode.
q Treat the drain pan with a plating product like Virginia Pan Tabs. Verify that the product you use is non-toxic, non-corrosive and will not
leave deposits that could damage the unit and drain pan.
Note: Treating the drain pan helps eliminate problems such as odor, overflow and water damage by preventing plugged drain lines and openings.
q Inspect coils.
Cleanliness Inspection
q Check the condition of the drain pan and accumulation of debris in the pan. Clean as required.
Tripp Lite SRCOOL33K SEMIANNUAL MAINTENANCE CHECKLIST
Prepared By: __________________________________________________________________Date:______________________________________
Model Number_________________________________________________Serial Number______________________________________________
Perform all Monthly Maintenance Checklist tasks PLUS the following task:
q Inspect the evaporator and condenser coils and clean if required.
9