Row, Block, Angled Installation - Roth DWT plus 3 620 Instructions De Montage Et De Service

Masquer les pouces Voir aussi pour DWT plus 3 620:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Single tank installation /

Row, block, angled installation

single tank
installation
D
GB
Row (up to 5 tanks),
block (2-25 tanks)
and angled instal-
lation (3-14 tanks)
F
I
NL
Install pre-assemble suction assembly fitting with
an overfull prevention device on the 2nd tank
connection .
Fit the angled ventilation piece with compression
seal and flat seal Ø 85/Ø 68 × 3 mm onto the 4th
tank connection .
changing the connection configuration is
possible; in doing so, please ensure that the
supplied dip pipe is always installed in the
filling tube!
install tanks onto mounting frames and next to one
another in centre to centre distances of 780 mm
(use enclosed spacers). Screw fill-level meters into
the bushings on every 3rd tank connection.
Pre-assemble filling line, lubricate O-rings, remove
protective hoses from the nozzles.
Fit filling line onto the 1st connection row with dip
pipe installed .
4
5
1
2
3
18