All loads in the room turn OFF immediately after entering PnL, then one load will turn ON. This is Load #1, which is bound to switch button #1
and occupancy sensors as part of the Plug n' Go factory default setting. All switch buttons and sensors that are bound to this load have their
blue LED solid ON.
Step 2 Load selection
Press and release the Config button to step through the loads connected to the DLM Local Network. As each load
turns ON note the devices (switch buttons and sensors) that are showing a bright solid blue LED. These devices are
currently bound to the load that is ON. The blue LED on the room controller or plug load controller connected to the
load is also lit.
• To unbind a switch or dimmer button from a load, press the switch button while its blue LED is ON bright. The blue
LED goes dim to indicate the button no longer controls the load that is currently ON.
• To unbind an occupancy sensor, press the up () or down () adjustment button while its blue LED is ON. The
blue LED turns OFF to indicate the sensor no longer controls the load that is currently ON.
Pressing the switch button or sensor up () or down () again while the load is ON rebinds the load to the button or
sensor and the blue LED illuminates brightly.
Step 3 Exit Push n' Learn
Press and hold the Config button until the red LED turns OFF, approximately 3 seconds.
LEDs on a switch or
sensor don't light
The wrong lights and plug
loads are controlled
LEDs turn ON and OFF
but load doesn't switch
Lamps do not dim, or
lamps drop out at low dim
levels
Cet appareil est préréglé pour un fonctionnement
Plug n' Go™ et son réglage est optionnel.
Pour connaître tous les détails opérationnels, les réglages et
les fonctions supplémentaires du produit, consulter le guide
d'installation du système DLM fourni avec le contrôleurs de
pièce LMRC-102/11x/2xx et aussi disponible au www.legrand.us/
wattstopper.
L'installation doit être effectuée conformément à tous les
règlements ainsi qu'aux codes locaux et de la NEC en
vigueur. Les raccordements de fils doivent être classés comme
pouvant convenir au calibre du fil (fil de sortie et de bâtiment)
utilisé.
Pour les dispositifs DLM de classe 2 et le câblage du dispositif
: Doit être connecté à une source d'alimentation de classe 2
seulement. Ne pas reclasser et installer en tant que classe 1 ou
en tant que fil d'alimentation ou d'éclairage.
TROUBLESHOOTING
1. Check to see that the the device is connected to the DLM Local Network.
2. Check for 24VDC input to the device: Plug in a different DLM device at the device location. If the
device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller and/or plug load controller(s).
• If high voltage connections are good and high voltage is present, recheck DLM Local Network
connections between the device and the room controller(s).
Configure the switch buttons and sensors to control the desired loads using the Push n' Learn
adjustment procedure.
1. Make sure the DLM local network is not in PnL.
2. Check load connections to room controllers and/or plug load controllers.
1. Make sure a 0-10V dimming ballast and rapid start sockets are installed per the ballast
manufacturer's recommendation. Shunted sockets are typically not acceptable.
2. Check wiring per ballast manufacturer's instructions.
INSTRUCTIONS EN FRANÇAIS
SPÉCIFICATIONS
Tension d'entrée ................................................ 120/230/277 VCA, 50/60 Hz
Exigences pour la charge ................... Ne doit pas dépasser un total de 10 A
Chaque relais a une capacité de:
Incandescence ..............................................................10 A à 120 VCA
Ballast ....................................................................10 A à 120/277 VCA
E-Ballast .................................................................10 A à 120/277 VCA
Sortie de puissance au réseau local DLM ............. jusqu'à 150ma @ 24VCC
Sortie de gradation Classe 1 & 2, 0-10V synchronisant jusqu'à 50ma par canal
Caractéristiques du réseau local DLM pendant l'utilisation des
LMRC-111/112:
La basse tension est générée par le câble Cat 5e (LMRJ); courant
maximal 800mA. Supporte jusqu'à 64 adresses de charge, 48 dispositifs
de communication incluant jusqu'à 4 séries LMRC-10x et contrôleurs
LMPL-101. Topologie libre allant jusqu'à 305 m (1 000 pi) max.
Capacité de mesurage avec les modèles LMRC-111-M et LMRC-112-M fournit
un mesurage en puissance avec une exactitude de 2% de la valeur réel
Capacité de mesurage de puissance lorsque utilisé avec LMSM Gestionnaire
de Réseau
Environnement ............................................. Pour usage intérieur seulement
Température de fonctionnement .................... 0 ° à 55°C (32 ° à 131°F)
Température d'entreposage ........................-5 ° à 80 °C (23 ° à 176 °F)
Humidité relative ..........................................5 à 95 % (non condensée)
Pour endroit Plenum UL2043, Rencontre la norme ROHS
3
Config button &
red LED