No: 24178 – 12/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPL-201
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
LMPL-201-U is BAA and TAA compliant (Product produced in the U.S.)
This unit is pre-set for Plug n' Go™ operation, adjustment is
optional.
For full operational details, adjustment and more features of the product, see
the DLM System Installation Guide provided with Wattstopper room controllers,
and also available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and
NEC codes. Wire connections shall be rated suitable for the wire size (lead and
building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2
power source only. Do not reclassify and install as Class 1, or Power and
Lighting Wiring.
Line Voltage
(Class 1 wiring)
Plug Load
Controller
To Plug Load
(Class 1 wiring)
To Other
Electrical
Outlets
CONNECTIVITY
The LMPL-201 communicates to all other DLM
devices connected to the DLM Local Network.
Connections shown are for example only. The
low voltage LMRJ cables can connect to any
DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG.
CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.
PLACEMENT EXAMPLES
J-Box
Switch
Ceiling Mount
Occupancy
Sensor
Corner Mount
Switch
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT –
IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Wattstopper
DLM Enhanced Digital Single Relay Plug Load Controller
Relais numérique simple amélioré – Contrôleur de prises DLM
Controlador DLM de un solo relé para receptáculo de CA
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
Input Voltage .................................................... 120VAC, 50/60Hz
Load Rating:
Maximum Duplex Receptacle Rating ...............120VAC, 20A
Connection to the DLM Local Network .................... 4 RJ-45 ports
DLM Local Network characteristics when using LMPL-201 room
controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 and/or LMPL-201controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 158°F (0° to 70°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
Line Voltage
(Class 1 wiring)
To Other
Electrical
Outlets
Ceiling Mount
Sensor
Sensor
Dimmer
LMPL or
LMRC series
Room Controller
®
SPECIFICATIONS
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Line Voltage
(Class 1 wiring)
J-Box
Plug Load
To Lighting
Controller
Load
(Class 1 wiring)
To Plug Load
(Class 1 wiring)
Line
DLM Local Network
Voltage
Low Voltage
LMRJ Cables
Plug Load
Controller
Deep J-Box
Black wire w/red stripe to Unswitched Receptacle
Room
Controller
J-Box
Switch
Ceiling Mount
Occupancy
Sensor
Earth Ground/Green wire
Line/Hot
Black wire
Neutral
White wire
Loads
Ground
Switched
Receptacle
Ground
Unswitched
Receptacle
Red wire to Switched Receptacle