No:22894 – 08/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMRC-102
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
LMRC-102-U is BAA and TAA compliant (Product produced in the U.S.)
This unit is pre-set for Plug n' Go™ operation, adjustment is optional.
For full operational details, adjustment and more features of the product, see the
DLM System Installation Guide provided with Wattstopper room controllers, and also
available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and
NEC codes. Wire connections shall be rated suitable for the wire size (lead and
building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2 power
source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.
WARNING: Do not install to cover a junction box having Class 1, 3 or Power and
Lighting Circuits.
Corner Mount
Occupancy
Sensor
Daylighting
J Box
Sensor
Ceiling Mount
Occupancy
Sensor
MOUNTING THE CONTROLLER
The LMRC‑102 room controller can be mounted external to either
a 4"x 4" or 4‑11/16 x 4‑11/16 junction box, placing it in the plenum
space or mounted directly inside a 4‑11/16 x 4‑11/16 junction box.
Outside a 4" x 4" or
4 11/16 x 4‑11/16 box
PLACEMENT EXAMPLE
DLM Local Network
(low voltage, Class 2)
LMRJ cables
Room
Controller
To
Load
J-Box
Inside a 4 11/16 x 4‑11/16 box
Wattstopper
Digital Lighting Management Dual Relay Room Controller
Gestion numérique de l'éclairage Contrôleur de pièce à relais double
Control de la iluminación digital Controlador de habitación de dos relés
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
DLM LOCAL NETWORK USE THE LMCI-100. NEVER
COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Switch
J-Boxes
Remove rubber jack covers if using all 3 RJ45 receptacles.
Leave covers in place for all unused receptacles.
®
SPECIFICATIONS
Input Voltage ...........................120/230/277VAC, 50/60Hz
Load Requirements ...................... Not to exceed 20A total
Each relay rated for up to:
Incandescent .....................................20A @ 120VAC
Ballast ....................................... 20A @ 120/277VAC
Motor ......................................... 1Hp @ 120/240VAC
Output .................................................... 150mA @ 24VDC
DLM Local Network Characteristics:
Provides low voltage power over Cat 5e cable (LMRJ).
Supports up to 24 communicating devices, including 4
LMRC‑10x or LMPL‑101 max per each DLM Local Network.
Free topology up to 1,000ft of low voltage cable.
Environment:
Operating Temperature ......32° to 104°F (0° to 40°C)
Storage Temperature ....... 23° to 176°F (‑5° to 80°C)
Relative Humidity ........... 5 to 95% (non condensing)
Patent Pending
WARNING: TURN THE
POWER OFF AT THE CIRCUIT
BREAKER BEFORE WIRING.
CAUTION: TO CONNECT A COMPUTER TO THE
CONNECT THE DLM LOCAL NETWORK
TO AN ETHERNET PORT – IT MAY DAMAGE
ATTACHING CABLES

Publicité

Table des Matières
loading

Sommaire des Matières pour LEGRAND Wattstopper LMRC-102

  • Page 1 DLM System Installation Guide provided with Wattstopper room controllers, and also Supports up to 24 communicating devices, including 4 available at www.legrand.us/wattstopper. LMRC‑10x or LMPL‑101 max per each DLM Local Network. Free topology up to 1,000ft of low voltage cable.
  • Page 2 CONNECTIVITY Corner Mount Ceiling Mount The LMRC‑102 communicates to all other DLM devices connected Line Sensor Sensor Voltage to the DLM Local Network. Connection drawings are for example DLM Local Network only. The low voltage LMRJ cables can connect to any DLM device Low Voltage LMRJ Cables with an open RJ45 receptacle.
  • Page 3: Spécifications

    Chaque relais a une capacité de : DLM fourni avec Wattstopper contrôleurs de pièce et aussi disponible au Incandescence ...........20 A à 120 VCA www.legrand.us/wattstopper. Ballast ............20 A à 120/277 VCA Moteur ............1 Hp à 120/240 VCA L'installation doit être effectuée conformément à tous les règlements Sortie ..............150 mA à...
  • Page 4: Fixer Les Câbles

    FIXER LES CÂBLES CONNECTIVITÉ Le LMRC‑102 communique avec tous les autres appareils DLM connectés au réseau local DLM. Les schémas de connexion sont à titre d'exemple seulement. Les câbles LMRJ à basse tension peuvent être connectés à n'importe quel appareil DLM qui possède une prise RJ45 ouverte.
  • Page 5: Dépannage

    Balasto ............20 A a 120/277 VCA proporciona con los controladores de habitación Wattstopper; también Motor ............1 HP a 120/240 V CA está disponible en www.legrand.us/wattstopper. Salida ..............150 mA a 24 V CC Características de red local DLM: La instalación debe realizarse conforme a todas las Suministra alimentación de bajo voltaje por un cable Cat 5e (LMRJ).
  • Page 6: Conexión De Cables

    EJEMPLO DE UBICACIÓN Cables LMRJ de ADVERTENCIA: DESCONECTE LA Red Local DLM (bajo voltaje, clase 2) ALIMENTACIÓN EN EL DISYUNTOR Sensor de Ocupación de ANTES DEL CABLEADO. Montaje en Esquinas Sensor de Controlador Caja de luz de día de habitación PRECAUCIÓN: PARA CONECTAR UNA conexiones COMPUTADORA A LA RED LOCAL DE DLM,...
  • Page 7: Solución De Problemas

    AJUSTE DE UNIDAD OPCIONAL: PUSH N’ LEARN (PNL) Procedimiento de selección de carga El botón de configuración (Config) permite el acceso a la tecnología Push n’ Learn™ patentada para cambiar las relaciones de unión entre sensores, interruptores y cargas. Paso 1 Entrar a Push n’ Learn Presione y mantenga presionado el botón Config (en cualquier dispositivo DLM) durante 3 segundos.
  • Page 8 No. 22894 – 08/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.

Table des Matières