LMRC-112 with Class 1 Dimming
Corner Mount
Ceiling Mount
Sensor
Sensor
Scene Switch
LMRC-111 with Class 1 Dimming
Line
Voltage
Line/Hot
Black wire
Neutral
White wire
Room
Controller
Deep J-Box
Red wire to Load
0-10V Gray and Violet wires to Load
Plug n' Go supports the most energy efficient control strategy. For example,
if at least two loads, one switch and one occupancy sensor are connected
to the DLM local network, the system operates load A as Automatic ON,
Automatic OFF and load B as Manual-On, Automatic-Off.
See DLM device Quick Start Guides to determine how each device affects
the PNG operation of the LMRC-111/112.
Load Control Arbitration
To take full advantage of automatic PnG configuration, review these simple
rules about load control arbitration.
After the room controllers are connected to the DLM Local Network and
powered up they automatically negotiate to determine which controller becomes the Master and
which load numbers are assigned to each relay on the DLM Local Network.
The Master is the controller with the most load relays and the highest serial number.
Example: In a DLM local network with only LMRC-112 room controllers, the LMRC-112 with the
highest serial number is the Master, carrying Load 1. The next highest serial number would have
Load 2, and so forth.
Load Selection Procedure
A configuration button (Config) allows access to Wattstopper's patented Push n' Learn™ technology to change binding relationships between
sensors, switches and loads.
Step 1 Enter Push n' Learn
Press and hold the Config button (on any DLM device) for 3 seconds.
The red LED on the LMRC-111/112 begins to blink. When you release the button, the red LEDs on other communicating devices
connected to the DLM Local Network begin to blink. They continue to blink until you exit PnL mode.
Line
DLM Local Network
Voltage
Low Voltage
LMRJ Cables
Room
Controller
Deep J-Box
Yellow wire to Load B
Red wire to Load A
0-10V striped wires to Load B
(Gray/Yellow and Violet/Yellow)
LMRC-111 with Class 2 Dimming
Room
Load
Controller
Switched with
0-10 Volt control
Dimming Ballast
LED Driver, etc.
Deep J-Box
Red wire to Load
0-10V Class 2 Dimming control wires
PLUG N' GO OPERATION (PNG)
UNIT ADJUSTMENT - PUSH N' LEARN (PNL)
O-10V Violet and Gray wires for Load A
(Not Used for a Switched Load)
Load
Line/Hot
Examples
Black wire
(any relay)
Neutral
Switched
White wire
A
etc.
Switched with
0-10 Volt control
B
B
Dimming Ballast
LED Driver, etc.
Line
Voltage
Line/Hot
Black wire
Neutral
White wire
Load
Switched with
0-10 Volt control
Dimming Ballast
LED Driver, etc.
0-10V Class 1 Gray and Violet wires
(not used)
Load A ON/OFF/Dim button
Load B
LMRC-112
Only
2
LMRC-112 with Class 2 Dimming
O-10V Gray and Violet wires for Load A
Line
(Not Used for a Switched Load)
Voltage
Line/Hot
Black wire
Neutral
White wire
Room
Controller
Deep J-Box
Yellow wire to Load B
Red wire to Load A
0-10V Class 1 striped wires (not used)
0-10V Class 2 Dimming control wires (available for each load)
0-10V Class 2 Connections
Tie-Down for
0-10V & LMRJ
cables
Load B
(LMRC-112 Only)
Blue LED ON when load
Load A
is ON.
Load button:
Press & release for ON/
OFF.
Press & hold to Dim.
Serial
Number
Controller
LMRC-112
0461373638
LMRC-112
Master
0461373679
Load
Examples
(any relay)
Switched
A
etc.
Switched with
0-10 Volt control
B
B
Dimming Ballast
LED Driver, etc.
Load A
Gray (-)
Violet (+)
Room
Load
Control
3
A
0341373638
4
B
1
A
0341373638
2
B