(3) Calculation example
No.
Indoor unit 1
Duct type
Model
Duct type
Liquid pipe:
No.
Pipe size
Length
No.
Pipe size
Length
High pressure gas pipe:
1)Additional quantity of refrigerant for liquid pipe (kg)
Φ 9.52:A+B+C+D+e+a=5+30+10+5+5+10=65m
Φ 6.35: E+b+c+d=5+10+10+10=35m
NOTE!
If liquid pipe is within 20m, there is no need to add refrigerant.
Additional quantity of refrigerant for liquid pipe =(65-20)×0.054+35×0.022=3.2kg
2)Additional quantity of refrigerant for hydro box (kg)
Additional quantity of refrigerant for hydro box =0.3×1=0.3kg
3)Additional quantity of refrigerant for high pressure gas pipe (kg):
Φ 12.7:F=10m
Additional quantity of refrigerant for high pressure gas pipe =10×0.09=0.9kg
Therefore, the minimum additional quantity of refrigerant =3.2 + 0.3 + 0.9=4.4kg.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Indoor unit 2
Duct type
A
B
Φ9.52
Φ9.52
5m
30m
a
b
Φ9.52
Φ6.35
10m
10m
No.
Pipe size
Length
Fig.23
Indoor unit 3
Duct type
C
Φ9.52
10m
c
Φ6.35
10m
20
Indoor unit 1
Hydro box 5
Duct type
AQUABOX 16
Duct type
D
E
Φ9.52
Φ6.35
5m
5m
d
e
Φ6.35
Φ9.52
10m
5m
F
Φ12.7
10m