Rheem RTEH1812 Guide D'installation page 7

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EX07200-120 Rev A
Refer to the chart below for recommended copper wiring for conductors with a temperature rating of 75°C:
Non-thermostatic
Thermostatic
Tankless Electric Water
Tankless Electric
Heaters
Water Heaters
RTEH1812
RTEH1812T
RTEH2412
RTEH2412T
RTEH3012
RTEH3012T
RTEH3512
RTEH3512T
RTEH35
RTEH35T
RTEH48
RTEH48T
RTEH55
RTEH55T
RTEH65
RTEH65T
RTEH75
RTEH75T
RTEH95
RTEH95T
-
RTEH012240T
RTEH3208
RTEH3208T
RTEH4208
RTEH4208T
RTEH8208
RTEH8208T
RTEH3277
RTEH3277T
RTEH4277
RTEH4277T
RTEH60
RTEH60T
RTEH80
RTEH80T
RTEH90
RTEH90T
RTEH100
RTEH100T
Power cable entry to the heater should be made through one of
the knock-out holes located on the back plate or top/bottom
ends of the unit. Use the appropriate strain relief fitting.
The power leads are to be secured to the L1 and L2 or L and N
connectors on the terminal block or relay. The ground lead is to
be secured to the GND connector on the block or the green
ground wire with the provided wire nut.
FAILURE TO GROUND THE SYSTEM MAY RESULT IN SERIOUS INJURY, DEATH AND/OR PROPERTY
DAMAGE.
Manufacturer's National Service Department | 400 Captain Neville Dr. Waterbury, CT 06705
Eemax® 800-543-6163 | EcoSmart® 877-474-6473 | Rheem® or Richmond® 800-374-8806
Information contained in this document is subject to change without notice.
Thermostatic Tankless
Electric Water Heaters with
Integrated Mixing Valve
-
-
-
RTEH004120MV
-
RTEH005240MV
-
RTEH007240MV
-
RTEH010240MV
RTEH012240MV
-
-
-
-
RTEH004277TMV
-
RTEH008277MV
-
RTEH010277MV
Voltage
Max power
(VAC)
(kW)
120
1.8
120
2.4
120
3
120
3.5
240
3.5
240
4.8
240
5.5
240
6.5
240
7.5
240
9.5
240
11.5
208
3
208
4.1
208
8.3
277
3
277
4.1
277
6
277
8
277
9
277
10
Max current
Minimum wire
size (AWG)
(A)
@75°C
15
14
20
14
25
12
29
10
15
14
20
14
23
12
27
10
32
10
40
8
48
8
15
14
20
14
40
8
11
14
14.8
14
22
12
29
10
33
10
36
8
7

Publicité

Table des Matières
loading

Table des Matières