Unit Programming; Notes; Technical Data - DOLD SAFEMASTER BG 5925 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Unit programming

Notes

Line fault detection on On-button:
The line fault detection is only active when S12 and S22 are switched
simultaneously. If The On-button is closed before S12, S22 is connected
to voltage (also when line fault across On-Button), the output contacts will
not close.
A line fault across the On-button which occurred after activation of the
relay, will be detected with the next activation and the output contacts
will not close. If a line fault occurs after the voltage has been connected
to S12, S22, the unit will be activated because this line fault is similar to
the normal On-function. The gold plated contacts of the BG 5925 mean
that this module is also suitable for switching small loads of 1 mVA - 7 VA,
1 mW - 7 W in the range 0.1 - 60 V, 1 - 300 mA. The contacts also permit
the maximum switching current. However since the gold plating will be
burnt off at this current level, the device is no longer suitable for switching
small loads after this (not for variant BG 5925.22/102).
The terminal S21 permits the operation of the device in IT-systems with
insulation monitoring, serves as a reference point for testing the control
voltage and is used to connect the E-stop loop when cross fault moni-
toring is selected.
Connecting the terminal S21 to the protective ground bridges the internal
short-circuit protection of Line A2 (-). The short-circuit protection of line
A1 (+) remains active.
To alter the functions automatic start - manual start and with or without
cross fault monitoring, the switches S1 and S2 are used. These are loca-
ted behind the front cover (see unit programming).
The setting with or without cross fault monitoring on E-stop buttons is
made with S1. S2 is used to change between automatic an manual restart.
On automatic start also the terminals S33 - S34 have to be linked. For
connection please see application examples.
Platte

Technical Data

Input circuit
Nominal Voltage U
Voltage range
at 10% residual ripple:
at 48% Rresidual ripple:
Nominal consumption:
Min. Off-time:
Control voltage on S11:
Control current over
S12, S22:
Min. voltage between
terminals S12, S22 and S21: DC 21 V when relay activated
Short-circuit protection:
Overvoltage protection:
Output
Contacts
BG 5925.02:
BG 5925.03:
BG 5925.16:
BG 5925.22:
The NO contacts are safety contacts.
The NC contacts 21-22 or 31-32 can only be used for monitoring.
Operate delay typ. at U
Manual start:
automatic start:
BG 5925._ _ /101:
Release delay typ. at U
Disconnecting the supply:
Disconnecting S12, S22:
Contact type:
Nominal output voltage:
Switching of low loads:
(contact 5 µ Au)
(contact AgNi)
Thermal current I
on 1 contact path:
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
Electrical contact life
to AC 15 at 2 A, AC 230 V:
to DC 13 at 1 A, DC 24 V:
Permissible operating
frequency:
Short circuit strength
max. fuse rating:
line circuit breaker:
Mechanical life:
16
BG 5925
BG 5925._ _/101
BG 5925._ _/102
BG 5925._ _/103
BG 5925._ _/104
Disconnect unit before setting of S1
Drawing shows setting at the state of delivery
M5986
:
DC 24 V, AC/DC 24 V
N
0.9 ... 1.1 U
0.8 ... 1.1 U
DC approx. 2 W
250 ms
DC 23 V at U
40 mA at U
and U
Internal PTC
Internal VDR
2 NO contacts
3 NO contact
1 NO, 1 NC contact
2 NO, 1 NC contact
:
N
40 ms
250 ms
100 ms
:
N
50 ms
15 ms
forcibly guided
AC 250 V
DC: see arc limit curve
≥ 100 mV
≥ 1 mA
≥ 10 mA / DC 24 V
:
th
max. 5 A
see current limit curve
3 A / AC 230 V
1 A / AC 230 V
1 A / DC 24 V
1 A / DC 24 V
4 A / 24 V at 0.1 Hz
4 A / 24 V at 0.1 Hz
10
> 1.5 x 10
max. 1 200 operating cycles / h
6 A gG / gL
C 8 A
10 x 10
S1
S2
Function
available in
unti
yes
yes
yes
yes
no
no
automatic + without
no
no
manual + with
no
no
automatic + with
DC
AC/DC
0.95 ... 1.1 U
N
N
0.8 ... 1.1 U
N
N
N
N
on A1 - A2
N
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1
switching cycles IEC/EN 60 947-5-1
5
switching cycles
5
IEC/EN 60 947-5-1
switching cycles
6
BG 5925 / 13.12.18 en / 048A