IF-LON
GENERAL
The CentraLine IF-LON L
ON
connect CentraLine controllers (via their USB port) with
L
W
® networks.
ON
ORKS
BEFORE INSTALLATION
All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
IF-LON network wiring can be sized from 1.5 to 0.34 mm
depending on the application. The maximum length of wire
from the CentraLine controller to the IF-LON is 0.8 m.
CAUTION
EMI Noise Introduction. Risk of erratic system
operation.
Keep wiring at least 300 mm away from large induc-
tive loads such as motors, line starters, lighting
ballasts and large power distribution panels. During
installations, try to avoid areas of high EMI noise.
Run IF-LON wiring separately from 50 Vac or greater
power wiring.
WARNING / CAUTION
Risk of electric shock or equipment damage!
Disconnect the power supply before making connections
►
to or removing connections from the IF-LON's terminals.
Do not reconnect the power supply until you have com-
►
pleted the installation.
Observe precautions for handling electrostatic sensitive
►
devices.
Copyright © 2013 Honeywell GmbH ● All Rights Reserved
W
® Interface can be used to
ORKS
Mounting Instructions
INSTALLATION
The delivery comes complete with the following parts:
IF-LON L
W
ON
USB cable (0.8 meter long);
Clamp for connection of the IF-LON Interface to the
L
W
network;
ON
ORKS
A DIN rail-mounting bracket;
These Mounting Instructions (MU1Z-0974GE51).
Software Installation
The necessary driver software is already installed on the
CentraLine controller.
If you have installed CARE on a PC having Windows 7 as
the operating system, no further user action is necessary.
If you have installed CARE on a PC having Windows XP
as the operating system, you will have to install usbnet.
See CARE – Installation Guide (EN1Z-0964GE51) for details.
Hardware Installation
Using the supplied USB cable, connect the IF-LON Interface
2
,
to a free USB port of the CentraLine controller (see Fig. 1).
NOTE:
In performing this action, it is not necessary to
remove the CentraLine controller from power.
2
3
Fig. 1. Connecting the IF-LON
no.
term
LonWorks® connector
1
STATE LED (green)
2
3
SERVICE LED (yellow)
4
Service Pin Button
5
USB connector
See also IF-LON Interface – Installation Instructions (MU1B-
0538GE51) for more-detailed information.
®
Interface;
ORKS
1
4
Table 1. Legend
2-pin:
TP/FT-10
OFF:
not ready to operate
ON:
ready to operate
Display Service Pin Neuron
processor
Manual activation of a Service
Pin message
Use supplied USB cable
MU1Z-0974GE51 R0913
5