Step 2. Wiring the panel heater to the control box
9
S-module
[Fig. 9.2.0.1]
<A>
A
B
[Fig. 9.2.0.2]
<A>
C
B
[Fig. 9.2.0.3]
D E F
B
<Heater>
Location of panel heater
wiring connection
Left side
Right side
Rear side
<A> Fasten the panel heater wirings with the wire saddles on the main control box
and the inverter control box.
A Panel heater wirings
B Wire saddle
<A> Route the panel heater wirings into the inverter control box through the rubber
bush.
Fasten the panel heater wirings together with the fan motor electrical wiring and
the terminal assy wiring with a cable strap.
A Terminal assy wiring
B Panel heater wirings
C Cable strap
A
A
<A> Wire the panel heater wirings as shown in the figure. Match the label
<B> CORRECT
<C> INCORRECT
* See the figure below for how to connect two ring terminals to a single
C
<A>
<CN510>
Wiring color Terminal block number
Yellow
1
Blue
1
White
2
9.2.0
color with the wiring color, and the label number with the wiring
number.
A Terminal
B Label
C Terminal assy wiring
D Left panel heater wiring (yellow)
E Right panel heater wiring (blue)
F Rear right panel heater wiring (white)
terminal.