Technical Data
Power circuit
Devices with Operating voltage AC/DC 24 V
Operating voltage range
Residual ripple DC
Rated power DC
Rated power AC
AC
Switch ON peak current (A1)
Rated short-circuit current
Operate time / recovery time
Protection for control circuit supply
galvanische Trennung Versorgungskreis-Steuerkreis
Devices with Operating voltage AC 100V/115V/200V/230V
Operating voltage range U
= AC 100 V
N
Operating voltage range U
= AC 115 -120 V
N
Operating voltage range U
= AC 200 V
N
Operating voltage range U
= AC 230 V
N
Rated power
Rated frequency AC
Protection for control circuit supply
Isolation supply circuit / control circuit
Control circuit
Conductor resistanc in Y1-Y2 / Y1-Y3 ( at U
supply voltage)
Rated output voltage to supply input Y2
Open circuit voltrage
Rated current / peak current (inputs Y2, Y3)
Release time t
(K1, K2)
R
Operate time t
(device with operating voltage AC 115 -120 V
A1
/ AC 230 V)
Operate time t
device with operating voltage AC/DC 24 V)
(
A1
Operate time t
A2
Minimum ON time t
(Y2)
M1
Minimum ON time t
(Y3)
M2
Recovery time t
W
Ready time t
B
Output circuit
Contact equipment
Rated switching voltage U
n
Max. continuous current I
per current path NO/NC
n
Max. total current for all current paths for devices with
operating voltage AC/DC 24 V
Max. total current for all current paths for devices with
operating voltage AC 115 -120 V / AC 230 V
Utilization category according to EN 60947-5-1
Mechanical service life
short-circuit protection, fuse
General data
Clearance/creepage distance between circuits
Overvoltage category
Rated impulse withstand level
Rated voltage
Power-frequency test voltage
Contamination level of device: inside / outside
Protection class to EN 60529 Housing / terminals
Ambient / storage temperature
Weight for devices with operating voltage AC/DC 24 V
Weight for devices with operating voltage AC 115 -120 V / AC 230
V
Terminals and connection
Single-core or finely stranded
Finely stranded with wire-end ferrule to DIN 46228
Max. tightening torque
Stripping length
6
AC/DC 20.4 V
AC 90 V
AC 93.5 V
AC 180 V
AC 195 V
regardless of
N,
3 enabling current paths with positively driven contacts (NO), 1 signalling current path
screw-type terminals
1 x 0.2 - 2.5 mm² / 2 x 0.2 - 1.0 mm²
1 x 0.25 - 2.5 mm² / 2 x 0.25 - 1.0 mm²
min.
typ.
AC/DC 24 V
--
1.3 W
--
1.8 W / 3.2 VA
50 Hz
--
--
--
--
1400 mA
--
2 s / 3 s
PTC thermistor
No
AC 100 V
AC 115 -120 V
AC 200 V
AC 230 V
--
2.0 W / 2.3 VA
50 Hz
--
Short-circuit-proof transformer
Yes
--
--
--
DC 24 V
--
--
--
--
--
60 ms
--
180 ms
--
40 ms
--
40 ms
t
--
A1
t
--
A2
--
--
--
--
(NC)
AC 230 V
8 A / 5 A
12 A
8 A
AC-15: Ue AC 230 V, Ie 5 A
DC-13: Ue DC 24 V, Ie 5 A
6
10 x 10
switching operations
max. 8 A
to EN 60664-1
depending on device version, see Isolation supply circuit
AC 300 V
IP 40/IP 20
-25 ... +55 / -25 ... +75 °C
0.20 kg
0.25 kg
0.5 to 0.6 Nm
max. 7 mm
max.
AC/DC 26.4 V
2.4 V
SS
1.6 W
2.2 W / 3.9 VA
60 Hz
1.7 A
--
--
AC 115 V
AC 132 V
AC 230 V
AC 253 V
2.4 W / 2.8 VA
60 Hz
70 
DC 40 V
90 mA / 1500 mA
80 ms
300 ms
60 ms
60 ms
--
--
200 ms
300 ms
III
4 kV
2 kV
2 / 3
spring-type terminals
1 x 0.2 - 1.5 mm²
1 x 0.25 - 1.5 mm² (trapezoid crimping)
---

Publicité