Les langues disponibles

Type
MBT 9110 Standard:

Electrical specifications:

Specifications range:
-40°C to +85°C
Common specifications:
Supply voltage, DC
MBT 9110, 084Z7440 ........................................ 8...35 V
Standard ATEX, MBT 9110, 084Z7441 ........ 8...30 V
Internal consumption ................................................ 25 mW...0.8 W
Voltage drop ................................................................. 8 VDC
Warm-up time .............................................................. 5 min.
Communications interface ...................................... Loop Link
Signal / noise ratio ...................................................... Min. 60 dB
Response time (programmable) ............................ 0.33...60 s
Signal dynamics, input .............................................. 19 bit
Signal dynamics, output ........................................... 16 bit
Calibration temperature ........................................... 20...28°C
Accuracy, the greater of general and basic values:
Input type
All
IC.PS.P40.A3.ML/520B2284
Version
Standard Atex: 084Z7441
General values
Absolute
accuracy
≤ ±0.1% of span
084Z7440
Temperature
coefficient
≤ ±0.01% of span / °C