Danfoss MBT 9110 Manuel D'installation page 21

Masquer les pouces Voir aussi pour MBT 9110:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

NAMuR NE43 upscale ............................................... 23 mA
NAMuR NE43 Downscale ......................................... 3.5 mA
EEx approval MBT 9110, 084Z7441:
KEMA 04ATEX1339 .......................................................
Max. amb. temperature for T4 ................................ 85°C
Max. amb. temperature for T6 ............................... 60°C
ATEX, applicable in zone............................................. 0, 1, 2, 20, 21 or 22
. .
ATEX Installation Drawing No. ........................ MBT 9110 084Z7441
Observed authority requirements: ............. Standard:
EMC 2004/108/EF ...... Emission and immunity ....EN 61326-1
ATEX 94/9/EC ...................................................................EN 60079-0, EN 60079-11,
. .
. .
Of span = Of the presently selected range
IC.PS.P40.A3.ML/520B2284
II 1 G Ex ia IIC T4 or T6
II 1 D Ex iaD
EN 60079-15, EN 60079-26,
EN 61241-0, EN 61241-11
19