Installation
Installation
Supplies Required:
• (4) 5/8" floor anchors and bolts
• Pipe sealant and teflon tape
• Piping to 2" PVC water supply inlet on unit
• Piping to 2" PVC drain outlet for eye wash on unit
• Adequate supply pipe supports
• Minimum 4" (102mm) drain to accommodate 30 gallons
per minute discharge for drench shower waste
• OPTIONAL: sign-mounting hardware
NOTE: Local codes may require the installation
of a backfl ow prevention valve to complete proper
installation. Compliance with local codes is the
responsibility of the installer. Valve must be tested
annually to verify that it is functioning properly. Backfl ow
prevention valves are not included with the fi xture and
may be supplied by the contractor or purchased from
Bradley Corporation.
IMPORTANT: Do not rely on Bradley's
Combination Unit to support supply piping.
Step 1: Assemble and Install Drench Shower
1. Install four suitable anchors (supplied by installer)
for 5/8" bolts in the floor.
2. Bolt the base to the floor anchors using 5/8" bolts
(supplied by installer).
3. Assemble the remaining drench shower
components as shown on page 4.
• Apply pipe sealant (by installer) to all male-
threaded pipe joints.
• The bottom edge of the showerhead should be
7'-0" (2134mm) from the floor.
4. Connect the water supply piping to the 2" PVC
inlet on the unit (piping by installer). Provide
adequate supports (supplied by installer) for
supply pipe using pipe hangers or other means.
5. Connect the drain piping to the 2" PVC drain outlet
on the unit (piping supplied by installer).
Step 2: Assemble and Install Eye/Face Wash
NOTE: See pages 4–5 for part identifi cation.
1. While holding the elbow in the lower assembly
piping, thread pipe #113-946 (Item #21) through
the hole in the lower assembly piping, and connect
to the elbow.
2. Install the reducer on top of the elbow.
3. Center the elbow, then tighten the pipe #113-946
(Item #21) in place.
4. Install the union and pipe nipple on pipe #113-946
(Item #21).
5. Place the gasket, then the strainer, on top of the
lower assembly piping.
6. Place the eyewash bowl on top of the strainer.
7. Install the yoke assembly by connecting the
stainless steel pipe, at the base of the yoke
assembly, to the reducer on the elbow.
8. Connect the pipe nipple to the valve piping
assembly.
Bradley Corporation • 215-1134 Rev. S; ECN 08-512
26-3/8"
(670mm)
4-1/2"
(114mm)
Ø 3.1"
(78.7mm)
9"
(229mm)
7'-0"
(2134mm)
to fl oor
43-3/8"
(1100mm)
(4) Ø 3/4" (19mm)
Holes on Ø 4-3/4"
(121mm) Bolt Circle
NOTE: All dimensions assume standard thread
engagement. Variations in manufacturing allow for
+/- 1/8" (3mm) per threaded joint. To fi nd the tolerance
of a dimension, add the number of thread joints in
between a dimension and multiply it by 1/8" (3mm).
9/11/08
S19-310PVC
66"
(1676mm)
to fl oor
36"
(914mm)
8"
(203mm)
3