REG FILTER REGULATOR CONFIGURABLE PARAMETERS
To access the parameters mode, in normal operating mode press MODE continuously (approx. 2s) until the user menu appears
on the screen (date setting, time programming, identifier, parameters, reset of the G4 filter operating time, reset of the operating
time filter H14 and regulator reset). With the UP and DOWN keys select PAr and press MODE, accessing the parameter mode
at that moment.
Note: During parameter mode, the regulator does not communicate on the serial communication channel.
In parameter mode the functions of the buttons are as follows:
- ON/OFF: Exits parameter mode.
- MODE: Accepts the value of the displayed parameter and goes to the next parameter.
- GO UP: Increases the value of the parameter.
- GO DOWN: Decrease the value of the parameter.
Parameter list
P1. RUNNING HOURS G4 FILTER FOR DIRTY FILTER INDICATION (range: 0ff, 00001h to 09000h; default: 04000h
OFF Function disabled
00001...09000 Function enabled
P2. HOURS OF OPERATION FILTER H14 FOR DIRTY FILTER INDICATION (range: 0ff, 00001h to 09000h; default: 07305h)
OFF Function disabled
00001...09000
Function enabled
P3. MINIMUM VOLTAGE FAN SPEED (range: 0.0V to 5.0V; default: 2.0V)
P4. MAXIMUM VOLTAGE FAN SPEED (range: 6.0V to 10.0V; default: 9.5V)
P9. COMMUNICATIONS ADDRESS (range: 1 to 240; default: 1)
In schedule, indicates the copy of the day.
Weekday.
In hourly programming it indicates the day of the week that is being programmed.
Wifi connection error.
In model with wifi connectivity.
Server connection error.
In model with wifi connectivity.