Initial Configuration - Vortice LINEO 100 V0 ES Notice D'emploi Et D'entretien

Masquer les pouces Voir aussi pour LINEO 100 V0 ES:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
ENGLISH

Initial configuration

The installer must configure appliance operation by
following the steps described later on.
selecting the product model: see below. This step is
carried out in the factory; the instructions provided in
this booklet may only be of use if it becomes
necessary to reset the status following accidental
tampering with the dip-switch.
selecting the operating mode: see below. There are
two modes: with two speeds V1 and V2, which can
be selected via an external switch, or with speed that
can be adjusted via an external potentiometer.
setting the V1 and V2 values (for two-speed operating
mode)
Selecting the product model
The model is selected by setting the dip-switch 1
indicated in the figure as described in the table below.
DIPSWITCH
SW 1 : MODEL
SW 2 : SETUP
2
1
TRIMMER
LINEO 100 Q V0 ES - LINEO 200 V0 ES
DIPSWITCH
SW 1 : MODEL
SW 2 : SETUP
2
1
TRIMMER
LINEO 250 V0 ES, LINEO 315 V0 ES
12
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
Model
LINEO 100 Q V0 ES OFF
LINEO 100 V0 ES
LINEO 125 V0 ES
LINEO 150 V0 ES
LINEO 160 V0 ES
LINEO 200 V0 ES
LINEO 250 V0 ES
LINEO 315 V0 ES
Selecting the operating mode
Two-speed mode:
cut off the power supply
set the dip-switch SW2 indicated in
the figure:
Int.2=ON; Int.3=OFF
Int.4=OFF
Adjustable speed mode:
cut off the power supply
set the dip-switch SW2 indicated in
the figure:
Int.2=OFF; Int.3=OFF
Int.4=OFF
Setting the V1 and V2 values
The appliance leaves the factory with default nominal
settings V1=V
, V2=V
MIN
Values V1 and V2 can be adjusted as follows:
- cut off the power supply
- set the dip-switch SW2 indicated
in the figure:
Int.1=OFF
Int.4=ON
- restore the power supply. The motor automatically
- set Int.1=ON. This produces two
effects:
the V1temp value is saved as a
new V1;
the motor automatically runs at V2temp;
- use the trimmer (see figure) to set V2temp to the
desired value, between the saved V1 + 100Rpm and
Vmax;
- set Int.1=OFF. This produces two
effects: the V2temp value is saved
as a new V2;
SW1
Int.1 Int.2 Int.3 Int.4
OFF
OFF
ON
OFF
OFF
OFF
OFF
1 2 3 4
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
1 2 3 4
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
MAX
ON
OFF
1 2 3 4
runs at the V1temp speed
- use the trimmer (see
figure) to set V1temp to the
desired
value,
between
V1nom and the saved V2 –
100Rpm
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
ON
OFF
ON
OFF
ON
OFF
ON

Publicité