1. USER GUIDE
Heat & cool module BT-HCM02-RF is specially designed to control your Under Floor Heating & Cooling system.
It is linked to your installation in RF (868MHz) via the BT-M6Z02 RF.
BT-HCM02-RF can get Heat/Cool signal from different sources:
-
input free contact from Heat Pump output
-
input free contact for a manual switch
-
a NTC sensor to measure the water temperature inlet
-
from the BT-CT02-RF (BT-HCM02-RF configured in slave mode)
BT-HCM02-RF has also some outputs for:
-
global pump of the system
-
Dehumidifier outputs in case of humidity default detected (in association with BT-D(P)02-RF RH thermostats)
-
Heat and Cool outputs to switch installation in Heating / Cooling
2. TECHNICAL CHARACTERISTICS
Operating Temperature
Supply Voltage
Outputs:
Heating and cooling
Humidity drier
Pump
Input:
HC
Radio Frequency
CE Directives
Your product has been designed in
conformity with the European
Directives.
Protection
Combination
230VAC +- 10% 50Hz
2 x Relay => 5A / 250VAC (Free contact)
1 x Relay => 5A / 250VAC (Free contact)
1 x Relay => 5A / 230 VAC ( L, N)
HC input could be connected to
a free contact for a manual switch or Heat Pump output
a CTN 10K to measure the water temperature
868,3 MHz <10mW.
Range of approximately 180 meters in open space.
Range of approximately 50 meters in residential environment.
R&TTE 1999/5/EC
EMC 2004/108/EC
Only with BT-M6Z02-RF
2
BT-HCM02 RF
0°C to 50°C
LVD 2006/95/EC
RoHS 2011/65/EU
IP 30