6
END-LIMIT ADJUSTMENT
6.1 - Checking rotation direction
It is essential to check the rotation direction of the motor to ensure proper operation of the limit switches.
Once the power supply is connected, replace the wiring cover :
- Tighten the 3 screws
- Switch on the installation.
- Move the shutter with the keyswitch.
If the output shaft is rotating in the opposite direction to the one
required :
- Immediately release the switch.
- Switch off the supply.
- Revert wiring of Cde S1 and Cde S2.
- Switch on again and check the rotation direction.
6.2 - End limit adjustment
S1/S2 arrows are placed around the shaft : spot which one corresponds to the upward movement.
Move the shutter. If the limit switch is not in the desired position, push in the screw corresponding
to the chosen direction (S1 or S2) with a screwdriver and :
- To increase the number of turns: Push and turn in the"+" direction.
- To decrease the number of turns: Push and turn in the"-" direction.
1
2
7
MAINTENANCE
SIMUBOX has been carefully designed and requires no special maintenance. However, it must be installed away
from splashing water. It is lubricated for life, the special lubricant should never be changed.
Any removal of the housing cover will void the warranty.
Consult us for any operation other than the motorization of grids and roll-up curtains.
- Tips and recommendations for installation:
PROBLEMS
The motorised product does
not operate.
The motorised product stops
at the end limit and no longer
operates.
SIMU SAS F-70103 GRAY hereby declares that the product covered by these instructions and used as indicated in these instructions, complies with the essential re-
quirements of the applicable European Directives and in particular with the Machine Directive 2006/42/EC and the EMC Directive 2014/30/EU. The full text of the EU
Declaration of Conformity is available at www.simu.com. Fabrice GLORIEUX, Director General, GRAY, 04/2018.
5/5
EN
If the motor does not operate, turn the limit switches 4 turns in the + direction. Repeat
the settings after releasing the stop.
POSSIBLE CAUSES
The overheating protection on the drive has
been activated.
The manual override system is active.
The motor is stopped at its security end
limit.
Following the use of the manual override
system, the security end limits device is
activated.
Direction 1
Direction 2
S1
S2
SOLUTIONS
Wait for the drive to cool down.
Release the troubleshooting maneuver to
deactivate it.
Call your maintenance staff to inspect the
installation.
Use the manual override system to turn the
tube 30° and deactivate the security end
limits device.