Wiring Diagram
Connecting the Main Sensor to the Remote
Connecting the Main Sensor to the Remote
Wire: Signal wiring should be done with #20-24 AWG shielded
twisted pair cable Belden 9841 or similar. Network units should have
no more than 2,000 ft (600 m) of #22 AWG wire. Smaller gauge sizes
are limited by the same resistance limit. The LED on the faceplate
blinks to indicate communication with the main unit.
6
Wiring Diagram
Figure 2. Connecting Main Sensor to Remote
The OUT1 and OUT2 connectors on the remote sensor's
terminal are not used. DO NOT connect any wires to these
locations.
3
E
Point Remote Gas Sensor User Manual