TROUBLESHOOTING
PROBLEM: Low or No Output Voltage – Fault LED Lit
Reason
Poor contact with battery, inverter
terminals.
PROBLEM: Inverter Auto Shut Down – Fault LED Lit
Reason
Battery voltage is below 10.0 volts.
Inverter is too hot (thermal shut down
mode).
PROBLEM: Inverter Shut Down – Fault LED Lit
Reason
Equipment being operated draws too
much power.
PROBLEM: No AC Output – Yellow Ground Fault LED Lit
Reason
Ground fault is unintended AC current
that is flowing to ground. It can be
caused by faulty wiring, bad insulation,
very long wiring, and sparking
appliances.
15
®
Solution
Clean terminals thoroughly. Reinstall
and tighten.
Solution
Charge or replace battery.
Allow inverter to cool.
Check for adequate ventilation.
Reduce the load on the inverter to
the specified TrueRated
max output.
Solution
Do not use the equipment with this
inverter; use a higher wattage inverter.
Solution
Turn inverter OFF (O) to reset it, then
to ON (I). IF the inverter immediately
shuts off, disconnect each appliance
or wiring until the inverter will stay
on after reset. Examine the wiring or
appliance for unintended connections.
Repair or replace as necessary.
www.wagan.com
power