DC CABLE GAUGE
Minimize cable losses by using the thickest wire available and the shortest
practical length.
Measure Round Trip (RT) cable distances in feet. Round Trip cable distance is
battery to inverter and back to battery. If the application is in a vehicle with
engine operating, use the supplied cables for round trip distances up to 5 feet.
Use a recommended ANL fuse and Fuse holder. Fuse at 300 Amps. ANL fuses
are quick acting and sealed so they do not spark when they blow. Place fuse no
more than one foot from the Positive (+) terminal of the battery.
Cable length (feet)
Gauge (AWG)
CONNECTING THE INVERTER
Installation procedure:
1. Mount the inverter in a secure location. If the inverter is to be mounted on a
wall, mount it horizontally. Make sure that the front and rear of the inverter
has free air flow.
2. Make sure the cables are the proper gauge and have the fuse holder as
close to the battery bank's Positive (red) terminal.
3. Install the fuse in the Positive (red) cable.
11
®
8
9–10
11–14 15–17 18–21
0
2/0
3/0
www.wagan.com
22
2/0
3/0
4/0
×2
×2
23–25
4/0
×2