10 - CONTROL
10.8 ALARMS
Code
Description
System high pressure protection:
Unit 300 : >=3.0Mpa active; <=2.4MPa inactive.
P1
Unit 190 : P1 error code never appear because pressure
switch
High discharge temperature protection
Unit 190/300 : >115 °C Protection active;
P2
<90 °C Protection inactive
Compressor abnormally stopped protection
The discharge temperature is not so higher than
P3
evaporator temperature after compressor running a
term.
Compressor overloaded protection (10 sec after
compressor startup, Current checking starts ,
1) only compressor running, if it is >10A , the
P4
compressor will be stopped and protected.)
2) Compressor + e-heater opened, if it is >IEH+10,the
compressor will be stopped and protected.)
When the ambient temp T4 is out of Heat Pump running
range (-7 ~ 43 °C ) Heat Pump will stop, unit will show
LA on the position of clock on display until T4 back to (-7
LA
~ 43 °C).
Only valid for the unit without e-heater.
Unit with e-heater will never show "LA".
The alarm codes listed above are the most common. If a alarm code not listed above is displayed, contact technical assistance.
If any of P3/P4/P2/P1 continuously appear 3 times within single heating cycle, system will consider it as "Heat Pump system error".
Contact a qualified person to service the unit.
Solution
Maybe because of system blocked, air or water or more
refrigerant in system (after repair), water temperature sensor
malfunction, ect.
Contact a qualified person to service the unit.
Maybe because of system blocked, air or water or less
refrigerant(leakage) in system( after repair), water temperature
sensor malfunction, ect.
Contact a qualified person to service the unit.
Maybe because of compressor broken or bad connection
between PCB and compressor.
Maybe because of compressor broken, system blocked, air or
water or more refrigerant in system(after repair), water
temperature sensor malfunction, ect.
Contact a qualified person to service the unit.
It is normal, and no necessary to repair.
TAB
44